Company
Innovationen
Products
The picture may show a similar product.
Part No.: 31039000
connection terminal, front connection
6 - 35 mm² / AWG 10 - 1/0
for 31548
Product group | 07 |
Subgroup | 26 |
pack size | 10 |
EAN | 4021267310394 |
ECLASS 6.1 | 27371390 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Standards
IEC 61439-1:2020
UL 508
Approvals
UL
for UL feeder circuits >250V
type number: CTB-T35.1
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
Rated current (IEC): | 115 A |
rated voltage (IEC) AC: | 690 V |
rated surge voltage Uimp : | 4 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 0,0 W.
(The power dissipation at full load would be 0,0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 690 V |
max. permitted voltage (IEC) DC: | 1000 V |
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 115 A |
rated voltage (UL) AC: | 1000 V |
rated frequency (UL): | 50 / 60 Hz |
rated voltage (UL) DC: | 1000 V |
SCCR unprotected max.: | 10 kA |
3 cycles (without OPD) @ 600 V AC |
SCCR: | 100 kA with fuse Class J 200 A |
Mechanical data | |
W x H x D: | 17 x 41 x 29 |
weight: | 3,0 kg/100 |
Terminal points | |
min. cross-section: | 6 mm² |
max. cross-section: | 50 mm² |
Not suitable for aluminium cables ! | |
6 - 35mm² |
Not suitable for aluminium cables ! | |
The insulation performance of the article depends on the installation conditions. | |
Reference |
Recommended stripping of the insulation on the connection lead approx. 14mm |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com