Company
Innovationen
Products
The picture may show a similar product.
Part No.: 01438000A
CRITO®185Power
connection rail
3-pole
screw M12
connection top or bottom
for busbars 30, 40, 60, 80, 100, 120 x 10
System
185Power
Product group | 07 |
Subgroup | 57 |
pack size | 1 |
EAN | 4021267014384 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
type number: CRL185-800
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
Electrical data IEC | |
Rated current (IEC): | 800 A |
rated voltage (IEC) AC: | 690 V |
rated peak withstand current Ipk max.: | 54.1 kA |
rated short-time withstand current Icw (0.5 s) max.: | 25.9 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 172,8 W.
(The power dissipation at full load would be 270,0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 1000 V |
max. permitted voltage (IEC) DC: | 1500 V |
current capacity (IEC) max.: | 800 A |
Mechanical data | |
W x H x D: | 100 x 665 x 150 |
weight: | 484,0 kg/100 |
poles: | 3-pole |
for busbars: | 30, 40, 60, 80, 100, 120 x 10 |
CT can be integrated in the device: | ja |
CT can be integrated in the CT module: | ja |
Terminal points | |
screw connection | |
M12 | |
The insulation performance of the article depends on the installation conditions. | |
Reference |
For using more connection rails in parallel, a rated diversity factor according IEC 61439 should be taken into account. |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com