Company
Innovations
Products
The picture may show a similar product.
Part No.: 01188000
triple-T section busbar 1140 mm²
length 453 mm, tinned
System
60Classic, centre feed unit
Advantages of the product
Tin-plated Cu busbars considerably reduce the effort of preparing the contact points.
The Cu busbars are effective protected against aggressive media.
Product group | 06 |
Subgroup | 92 |
pack size | 1 |
EAN | 4021267011888 |
ECLASS 6.1 | 27370303 |
ECLASS 7.1 | 27370303 |
ETIM 4.0 | EC001522 |
ETIM 5.0 | EC001522 |
Standards
IEC 61439-1:2020
UL 508
Approvals
CSA , UL , DNV GL
for UL feeder circuits >250V
type number: HH1140-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 33,9 W.
(The power dissipation at full load would be 53,0 W.)
diagram current capacity (IEC) |
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V |
considering the permitted temperature rise at the concrete installation conditions the following capacity could be accepted by UL (file E197039 |
|
max. load acc. to UL 508: | 1800 A |
Notice the rated voltage of the used busbar support in the application. |
Mechanical data | |
W x H x D: | 453 x 30 x 70 |
weight: | 464,0 kg/100 |
cross-section: | 1.140 mm² |
Edge radius 0.5
Please respect the insulation characteristics of the busbar support for your application. | |
short-circuit withstandability: | see product description of the used busbar support |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com