Company
Innovations
Products
The picture may show a similar product.
Part No.: 01595 000A
CRITO®CrossBoard
connection module
150 mm², for rear feeding of the CrossBoard
3-pole
connection top or bottom
for CrossBoard 250 A 300 - 1100 mm
System
CrossBoard® 125A / 250A
| Product group | 07 |
| Subgroup | 48 |
| pack size | 1 |
| EAN | 4021267015954 |
| ECLASS 6.1 | 27141146 |
| ECLASS 7.1 | 27141146 |
| ETIM 4.0 | EC000001 |
| ETIM 5.0 | EC000001 |
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Approvals
UL
for UL feeder circuits >250V
type number: CR-B-114-A1
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
| Details IEC | |
| Standards | |
|
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
| Electrical data IEC | |
| rated current (IEC): | 250 A |
| rated voltage (IEC) AC: | 690 V |
| rated isolation voltage Ui AC: | 800 V |
| rated surge voltage Uimp : | 6 kV |
| rated peak withstand current Ipk max.: | 30 kA |
| Supplementary data IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
| max. permitted voltage (IEC) AC: | 800 V |
| max. permitted voltage (IEC) DC: | 800 V |
| current capacity (IEC) max.: | 250 A |
| Details UL | |
| Standards | |
| UL 508 |
| for UL feeder circuits >250V | |
| suitable for field-installed conductors |
| Electrical data UL | |
| rated current (UL): | 285 A |
| rated voltage (UL) AC: | 600 V |
| rated frequency (UL): | 50 / 60 Hz |
| for wires UL: | Cu 75°C |
| SCCR unprotected max.: | 10 kA |
| 3 cycles (without OPD) @ 600 V AC | |
| SCCR protected max.: | 100 kA |
| SCCR: |
100 kA with JDDZ fuse Class J 400 A / 600 V AC
65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC |
| Mechanical data | |
| W x H x D: | 114 x 222 x 57 |
| weight: | 96,4 kg/100 |
| poles: | 3-pole |
| front degree of protection: | IP20 |
| Terminal points | |
| Prismenklemme | |
| screw drive: | S4 |
| wire stripping: | 30 mm |
| min. cross-section: | 35 mm² |
| max. cross-section: | 150 mm² |
| Md min.: | 4,0 Nm |
| Md max.: | 6,0 Nm |
|
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
| min. cross-section UL: | AWG 2 |
| max. cross-section UL: | MCM 300 |
| torque (UL): | 35 - 53 lb-in |
| for wires UL: | Cu 75°C |
|
Connecting circular conductors: |
|
| Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
| The insulation performance of the article depends on the installation conditions. | |
|
Crossboards before production date November 2024 also suitable for 250 A (IEC + UL). Confirmation |
|
| for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com