connection module (01595)

The picture may show a similar product.

Description

Part No.: 01595000A

CRITO®CrossBoard

connection module

150 mm², for rear feeding of the CrossBoard

3-pole

connection top or bottom

for CrossBoard 250 A

NEW

System

CrossBoard® 125A / 250A

Product group 07
Subgroup 48
pack size 1
EAN 4021267015954
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Approvals

Standards

IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Approvals

UL

for UL feeder circuits >250V

type number: CR-B-114-A1

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
Electrical data IEC
rated current (IEC): 250 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 6 kV
rated peak withstand current  Ipk max.: 30 kA
Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) AC: 800 V
max. permitted voltage (IEC) DC: 800 V
current capacity (IEC) max.: 250 A
Details UL
Standards
UL 508
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
rated current (UL): 285 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
for wires UL: Cu 75°C
SCCR unprotected max.: 10 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
SCCR: 65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC
100 kA with JDDZ fuse Class J 400 A / 600 V AC
Mechanical data
W x H x D: 114 x 222 x 57
weight: 67.0 kg/100
poles: 3-pole
front degree of protection: IP20
Terminal points
screw clamp connection
screw drive: S4
wire stripping: 30 mm
min. cross-section: 35 mm²
max. cross-section: 150 mm²
Md min.: 4.0 Nm
Md max.: 6.0 Nm
Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
  
min. cross-section UL: AWG 2
max. cross-section UL: MCM 300
torque (UL): 35 - 53 lb-in
for wires UL: Cu 75°C
  

Connecting circular conductors:

35... 50 mm² / 2... 1/0 AWG

4Nm / 35 lb in

 

70... 150 mm² / 2/0 AWG... 300 kcmil

6Nm / 53 lb in

 

35... 95 mm² flexible conductors, circular stranded conductors, flexible conductors with wire-end ferrules DIN 46228-1 max. 30 mm

120... 150 mm² flexible and circular stranded conductors

 

Connecting flexible conductors:

4x - 10x 15,5mm  x 0,8 mm

6Nm / 53 lb in  

Application notes

Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
The insulation performance of the article depends on the installation conditions.

Reference

Crossboards before production date November 2024 also suitable for 250 A (IEC + UL). Confirmation

for UL feeder circuits >250V

Links

Downloads

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com