switch-disconnector 3-pole

The picture may show a similar product.

Description

Part No.: 33543 000

QUADRON 60Classic Speed

switch-disconnector 3-pole

box terminal, connection bottom, for door coupling rotary handle

160 A

double-breaking

operator independent switching (snap-action mechanism)

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

System

60Classic

Advantages of the product

With spring-controlled switch mechanism for frequent switching as per utilisation category "A"
Lockable in neutral position with up to 3 padlocks
FLAG indicator shows the switch setting double-breaking main contacts
Can be used as a mains disconnector as per IEC / EN 60204-1 (main switch)
Can also be used as an Emergency Off switch in combination with the door coupling twist handle
Main switch and Emergency Off switch only in combination with AC-23A/B
AC-23B (690V/125A), AC-23A (500V/125A)

CrossLink® adapter technology
Simple and safe clicking into place and making contact
Busbar supports can be mounted above each other for flat busbars

Switches can be installed 90° left/right horizontal, always with the same switch handle position

Compact dimensions (106mm wide)

Product group 14
Subgroup 20
pack size 1
EAN 4021267335434
ECLASS 14.0 27371403
ETIM 5.0 EC000216
ETIM 8.0 EC000216
ETIM 10.0 EC000216

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

type number: QCS-160

EAC Type: QCS

Technical data

Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
rated current (IEC): 160 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 8 kV
Utilisation category AC (IEC 60947-3) : AC-23B (690V/125A)
AC-23A (500V/125A)
AC-22A (690V/160A)
cond. short-circuit current with fuses (AC): 50 kA / 690 V (125 A)
approved wth fuse links of operation class: gG
rated short-time withstand current Icw (1.0 s) max.: 4.5 kA
rated making capacity: 7 kA
Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

further utilisation category DC (IEC 60947-3): 2 current paths (L1,L3) in series
DC-22B (220V/125A)
Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals.
When several devices are used side-by-side in continuous operation, the rated load factor specified in VDE 0660 Part 500 / EN 60 439-1, Table 1, must be observed.
Mechanical data
W x H x D: 106 x 200 x 155
weight: 208,0 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
degree of protection: IP20
Terminal points
cage clamp connection
screw drive: S4
wire stripping: 20 mm
min. cross-section: 1,5 mm²
max. cross-section: 70 mm²
re: 1.5 - 10 mm²
f: 1.5 - 70 mm²
f + AE: 1.5 - 70 mm²
(f + AE may not fit with max. cross-section)
Md min.: 5,0 Nm
Md max.: 6,0 Nm
Not suitable for aluminium cables !
Terminal space: 13x13
lam. Cu width: 9 - 13 mm
lam. Cu thickness: 1 - 10 mm
Material properties
halogen-free: No

Application notes

Not suitable for aluminium cables !

Links (Prices, CAD data)

Downloads

Accessories

connection accessories

33914 000
connecting terminal 120 mm²
front connection
for: QCS-NH00, QCS-160
More

further accessories

33908 000
pilot switch for monitoring the switch position
changeover 250 V AC / 5 A, 30 V DC / 4 A
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320
More

33910 000
door coupling rotary drive
black, with handle
door interlock can be activated, for padlocks
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320
More

33911 000
door coupling rotary drive
yellow-red, with handle
door interlock can be activated, for padlocks
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320
More

33912 000
extension shaft, 290 mm long
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320, CP-PV
More

33913 000
extension shaft, 490 mm long
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320, CP-PV
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com