busbar mounted fuse holder 1000 V (31572)

The picture may show a similar product.

Description

Part No.: 31572000AB

AMBUS®60Classic

busbar mounted fuse holder 1000 V

for fuses 10x38 IEC 60269-6

1-pole, for busbars 20 x 5/10

for busbars 20 x 5, 10

no longer available

System

60Classic

Product group 01
Subgroup 46
pack size 12
EAN 4021267315726
ECLASS 6.1 27142190
ECLASS 7.1 27142190
ETIM 4.0 EC002705
ETIM 5.0 EC002705

Approvals

Standards

IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016

UL 4248-1

UL 4248-19

Approvals

UL , CCC

for UL feeder circuits >250V

type number: AEL10x38/PV-20

UL file: E230163, UL category (for USA): IZLT2 https://www.ul.com

UL file 2: E342576, UL category+ (for USA): IZMR2 https://www.ul.com

UL file: E230163, UL category (for Canada): IZLT8 https://www.ul.com

CCC certificate: 2013010308654225

Technical data

for fuse links size: 10x38
fuse links acc. to standard: IEC / EN 60269-6
permitted power dissipation of the fuse-link: 4 W
Details IEC
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016
Electrical data IEC
Rated current (IEC): 30 A
rated voltage (IEC) DC: 1000 V

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 0,1 W.

(The power dissipation at full load would be 0,2 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) DC: 1050 V
for fuse links as per IEC 60269-6
gPV with power dissipation up to max. 4W
Details UL
Standards
UL 4248-1
UL 4248-19
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 30 A
rated voltage (UL) DC: 1000 V
SCCR: 33 kA
Mechanical data
W x H x D: 22.5 x 70 x 73
weight: 6,3 kg/100
poles: 1-pole
for busbars: 20 x 5, 10
Terminal points
cage clamp connection
screw drive: PZ2
wire stripping: 11 mm
min. cross-section: 0,75 mm²
max. cross-section: 25 mm²
Md min.: 2,0 Nm
Md max.: 2,5 Nm
Not suitable for aluminium cables !

Application notes

Not suitable for aluminium cables !
The insulation performance of the article depends on the installation conditions.
permitted power dissipation of the fuse-link: 4 W
for UL feeder circuits >250V

Links

Downloads

Accessories

01355000
busbar support
1-pole, attachable to 01603 or individual mounting, with integrated end cover
for busbars: 12, 20, 30 x 5, 10
More

31543000
cylindr. fuse link 8 A
1000 V DC, gPV
10 x 38
More

31544000
cylindr. fuse link 10 A
1000 V DC, gPV
10 x 38
More

31545000
cylindr. fuse link 12 A
1000 V DC, gPV
10 x 38
More

31546000
cylindr. fuse link 16 A
1000 V DC, gPV
10 x 38
More

31547000
cylindr. fuse link 20 A
1000 V DC, gPV
10 x 38
More

Find your contact