Company
Innovationen
Products
for UL feeder circuits >250V
The picture may show a similar product.
Part No.: 36009000A
EQUES®CrossBoard
adapter 16 A
1 fixed mounting rail, with fuse-carrier 10x38 / Class CC
22.5 x 160, with leads AWG 14 (2.5 mm²)
System
CrossBoard® 125A / 250A
Advantages of the product
Leitungsenden ultraschallverdichtet.
Product group | 05 |
Subgroup | 21 |
pack size | 1 |
EAN | 4021267360092 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Standards
IEC 61439-1:2020
UL 508
Approvals
IEC (CB) , UL
for UL feeder circuits >250V
type number: EQ22-A1
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
Rated current (IEC): | 16 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 800 V |
rated surge voltage Uimp : | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 2,6 W.
(The power dissipation at full load would be 4,0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 725 V |
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 12.5 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 6 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 50 kA |
with JDDZ fuse Class CC 20 A / 600 V AC |
Mechanical data | |
W x H x D: | 22.5 x 160 x 85 |
weight: | 12,9 kg/100 |
poles: | 3-pole |
Reference |
Cylindric fuses are not included You find here recommended fuses
|
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com