in-line fuse switch-disconnector 910 A (33000)

The picture may show a similar product.

Description

Part No.: 33000 000A

QUADRON®185Power

in-line fuse switch-disconnector 910 A

Size NH 3

size 3, 1-pole switchable

standard connection

for busbars 60, 80, 100, 120 x 10

NEW

System

185Power

Product group 12
Subgroup 46
pack size 1
EAN 4021267330002
ECLASS 6.1 27142108
ECLASS 7.1 27142108
ETIM 4.0 EC001046
ETIM 5.0 EC001046

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

type number: QJ185-910/1-ST

Technical data

for fuse links size: NH 2, NH 3
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 61 W
Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
rated current (IEC): 910 A
rated voltage (IEC) AC: 400 V
rated isolation voltage Ui AC: 690 V
rated surge voltage Uimp : 8 kV
Utilisation category AC (IEC 60947-3) :

AC-22B (400 V / 910 A)

cond. short-circuit current with fuses (AC): 80 kA / 400 V (910 A)
approved wth fuse links of operation class: gTr
rated short-time withstand current Icw (1.0 s) max.: 10 kA
Icw approved with: Trennmesser

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 99.2 W.

(The power dissipation at full load would be 155.0 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

further utilisation category AC (IEC 60947-3): AC-22B (400 V / 1200 A) with cutting knife
Mechanical data
W x H x D: 100 x 868 x 194
weight: 574.0 kg/100
poles: 3-pole
for busbars: 60, 80, 100, 120 x 10
CT can be integrated in the device: nein
CT can be integrated in the CT module: nein
front degree of protection: IP30
vertical installation position: Yes
horizontal installation position: Yes

Type of fastening:
can be screwed onto drilled busbar, diameter 13mm, undrilled mounting with terminal clamp
connection:
screw connection M12

Terminal points
screw connection
M12

Application notes

permitted power dissipation of the fuse-link: 61 W