bornier de raccordement (01593)     PCF: 1,92 kg CO2e

The picture may show a similar product.

Description

Référence 01593000A

CRITO®CrossBoard

bornier de raccordement

avec bornes à cage 6 - 50 mm² / AWG 10 - AWG 1

3 pôles

Système

CrossBoard® 125A / 250A

Avantages produit

direct connection to the CrossBoard, cover included

capable of feeding (up to 125 A) 1 or 2 CrossBoards simultaneously with balanced or unbalanced load on the boards.

can be used without cables as a bridge connection between 2 CrossBoards up to 125 A. Feeding a third CrossBoard with cables is acceptable, but the total current cannot exceed 125 A.

touch-safe

CRITO® unlockable from top or bottom

Groupe de produits 07
Sous-groupe 42
Dimensions de l'emballage 1
EAN 4021267015930
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Homologations

Normes

IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Approbations

UL

for UL feeder circuits >250V

Type: CR45-A

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

Homologation CCC: no certification required

Données techniques

Details IEC
Normes
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
Electrical data IEC
Courant assigné (IEC): 125 A
Tension assignée (IEC) CA: 690 V
rated isolation voltage Ui AC: 800 V
rated peak withstand current  Ipk max.: 15 kA
Supplementary data IEC

Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire.

Tension maximale IEC CA: 800 V
Tension maximale IEC CC: 800 V
current capacity (IEC) max.: 125 A
Details UL
Normes
UL 508
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
rated current (UL): 100 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR unprotected max.: 10 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
SCCR: 65 kA with any DIVQ/7 circuit breaker 100 A / 600 V AC
100 kA with any DIVQ/7 circuit breaker 100 A / 480 V AC
100 kA with JDDZ fuse Class J 175 A / 600 V AC
Charactéristiques mécaniques
L x H x P: 45 x 160 x 92
Poids: 25,0 kg/100
Pôles: 3 pôles
front degree of protection: IP20
Points de raccordement
cage clamp connection
screw drive: S4
wire stripping: 17 mm
min. cross-section: 6 mm²
max. cross-section: 50 mm²
Md min.: 5,0 Nm
Md max.: 6,0 Nm
  
min. cross-section UL: AWG 10
max. cross-section UL: AWG 1/0
torque (UL): 44 - 53 lb-in
  

6 - 50 mm² / AWG 10 - AWG 1
feindrähtig, direkt geklemmt oder mit Aderendhülse,
6 - 35 mm² Rundleiter mehrdrähtig,

(feindrähtig mit Aderendhülse eventuell nicht mit maximalen Querschnitt möglich)

Application notes

Les performances d'isolation de l'article dépendent des conditions d'installation.
for UL feeder circuits >250V

Links

Documentation

Accessoires

01604000A
couvercle de protection contre les contacts accidentels IP20
for connection module 01593
Plus

Trouver votre contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com