modulo di connessione (01593)     PCF: 1.92 kg CO2e

The picture may show a similar product.

Descrizione

Cod.art.: 01593000A

CRITO®CrossBoard

modulo di connessione

con morsetti a gabbia 6 - 50 mm² / AWG 10 - AWG 1

3p

Montaggio

CrossBoard® 125A / 250A

Vantaggi prodotto

direct connection to the CrossBoard, cover included

capable of feeding (up to 125 A) 1 or 2 CrossBoards simultaneously with balanced or unbalanced load on the boards.

can be used without cables as a bridge connection between 2 CrossBoards up to 125 A. Feeding a third CrossBoard with cables is acceptable, but the total current cannot exceed 125 A.

touch-safe

CRITO® unlockable from top or bottom

gruppo di prodotto 07
sottogruppo prodotto 42
pz/ conf. 1
EAN 4021267015930
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Certificazioni

Norme

IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Omologazioni

UL

for UL feeder circuits >250V

type no.: CR45-A

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

Omologazione CCC : no certification required

Dati tecnici

Details IEC
Norme
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
Electrical data IEC
corrente nominale (IEC): 125 A
tensione nominale (IEC) AC: 690 V
tensione nominale di isolamento Ui AC: 800 V
resistenza nom. alla corrente di picco Ipk max.: 15 kA
Supplementary data IEC

I seguenti valori sono stati rilevati tramite prove con determinate condizioni. Prima di progettare vostro impianto chiedere a Wöhner suddette condizioni.

tensione max. ammissibile (IEC) AC: 800 V
tensione max. ammissibile (IEC) DC: 800 V
corrente d'impiego max. (IEC): 125 A
Details UL
Norme
UL 508
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
corrente nominale (UL): 100 A
tensione nominale (UL) AC: 600 V
frequenza nominale (UL): 50 / 60 Hz
SCCR unprotected max.: 10 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
SCCR: 65 kA with any DIVQ/7 circuit breaker 100 A / 600 V AC
100 kA with any DIVQ/7 circuit breaker 100 A / 480 V AC
100 kA with JDDZ fuse Class J 175 A / 600 V AC
Valori meccanici
L x A x P: 45 x 160 x 92
peso: 25.0 kg/100
Poli: 3 poli
grado di protezione dal fronte: IP20
Connessioni
cage clamp connection
screw drive: S4
wire stripping: 17 mm
min. cross-section: 6 mm²
max. cross-section: 50 mm²
Md min.: 5.0 Nm
Md max.: 6.0 Nm
  
min. cross-section UL: AWG 10
max. cross-section UL: AWG 1/0
torque (UL): 44 - 53 lb-in
  

6 - 50 mm² / AWG 10 - AWG 1
feindrähtig, direkt geklemmt oder mit Aderendhülse,
6 - 35 mm² Rundleiter mehrdrähtig,

(feindrähtig mit Aderendhülse eventuell nicht mit maximalen Querschnitt möglich)

Application notes

La capacità di isolamento dell'articolo dipende dalle condizioni di installazione.
for UL feeder circuits >250V

Links

Downloads

Accessori

01604000A
protezione IP20
for connection module 01593
Di Più

Trova il tuo contatto

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com