Innovationen
Prodotti
The picture may show a similar product.
Cod.art.: 01593000A
CRITO®CrossBoard
modulo di connessione
con morsetti a gabbia 6 - 50 mm² / AWG 10 - AWG 1
3p
Montaggio
CrossBoard® 125A / 250A
Vantaggi prodotto
direct connection to the CrossBoard, cover included
capable of feeding (up to 125 A) 1 or 2 CrossBoards simultaneously with balanced or unbalanced load on the boards.
can be used without cables as a bridge connection between 2 CrossBoards up to 125 A. Feeding a third CrossBoard with cables is acceptable, but the total current cannot exceed 125 A.
touch-safe
CRITO® unlockable from top or bottom
gruppo di prodotto | 07 |
sottogruppo prodotto | 42 |
pz/ conf. | 1 |
EAN | 4021267015930 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Norme
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Omologazioni
UL
for UL feeder circuits >250V
type no.: CR45-A
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
Omologazione CCC : no certification required
Details IEC | |
Norme | |
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
Electrical data IEC | |
corrente nominale (IEC): | 125 A |
tensione nominale (IEC) AC: | 690 V |
tensione nominale di isolamento Ui AC: | 800 V |
resistenza nom. alla corrente di picco Ipk max.: | 15 kA |
Supplementary data IEC | |
I seguenti valori sono stati rilevati tramite prove con determinate condizioni. Prima di progettare vostro impianto chiedere a Wöhner suddette condizioni. |
tensione max. ammissibile (IEC) AC: | 800 V |
tensione max. ammissibile (IEC) DC: | 800 V |
corrente d'impiego max. (IEC): | 125 A |
Details UL | |
Norme | |
UL 508 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Electrical data UL | |
corrente nominale (UL): | 100 A |
tensione nominale (UL) AC: | 600 V |
frequenza nominale (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 10 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
SCCR: |
65 kA with any DIVQ/7 circuit breaker 100 A / 600 V AC
100 kA with any DIVQ/7 circuit breaker 100 A / 480 V AC 100 kA with JDDZ fuse Class J 175 A / 600 V AC |
Valori meccanici | |
L x A x P: | 45 x 160 x 92 |
peso: | 25,0 kg/100 |
Poli: | 3 poli |
grado di protezione dal fronte: | IP20 |
Connessioni | |
cage clamp connection | |
screw drive: | S4 |
wire stripping: | 17 mm |
min. cross-section: | 6 mm² |
max. cross-section: | 50 mm² |
Md min.: | 5,0 Nm |
Md max.: | 6,0 Nm |
min. cross-section UL: | AWG 10 |
max. cross-section UL: | AWG 1/0 |
torque (UL): | 44 - 53 lb-in |
6 - 50 mm² / AWG 10 - AWG 1 (feindrähtig mit Aderendhülse eventuell nicht mit maximalen Querschnitt möglich) |
La capacità di isolamento dell'articolo dipende dalle condizioni di installazione. | |
for UL feeder circuits >250V |
Trova il tuo contatto
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com