L'Entreprise
Innovationen
Produits
The picture may show a similar product.
Référence 33731000A
QUADRON®185Power
double barrette de séparation de fusibles 1250 A
à commutation tripolaire
vis M12, avec cache borne compris
pour jeux de barres 30, 40, 60, 80, 100, 120 x 10
Système
185Power
Avantages produit
Self-closing inspection holes are available in the cover.
Cover can be locked when closed.
Groupe de produits | 12 |
Sous-groupe | 55 |
Dimensions de l'emballage | 1 |
EAN | 4021267337315 |
ECLASS 6.1 | 27142109 |
ECLASS 7.1 | 27142109 |
ETIM 4.0 | EC001046 |
ETIM 5.0 | EC001046 |
Normes
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Type: QU185-3/2x
for fuse links size: | NH 3 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 48 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Details IEC | |
Normes | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
Courant assigné (IEC): | 1250 A |
Tension assignée (IEC) CA: | 690 V |
rated isolation voltage Ui AC: | 1000 V |
Tension assignée de tenue aux chocs Uimp: | 8 kV |
Catégorie d'emploi CA: | AC-20B (690 V) |
Catégorie d'emploi CC: | DC-20B max. voltage between the fuses: 800 V visible information required: Do not switch under load. |
cond. short-circuit current with fuses (AC): | 50 kA |
approved wth fuse links of operation class: | gG |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 243,2 W.
(The power dissipation at full load would be 380,0 W.)
Supplementary data IEC | |
Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire. |
Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence. |
version: connection bottom |
|
Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals. | |
Degree of protection IP20 at front, degree of protection near terminal depends on installation |
Charactéristiques mécaniques | |
L x H x P: | 200 x 890 x 190 |
Poids: | 1556,0 kg/100 |
pour jeux de barres: | 30, 40, 60, 80, 100, 120 x 10 |
CT can be integrated in the device: | ja |
front degree of protection: | IP20 |
degree of protection when open: | IP10 |
Type of fastening:
can be screwed onto drilled busbar, diameter 13 mm, undrilled mounting with terminal clamp
connection:
screw connection M12, max. 4/8 cable lugs for 300 / 240mm², for more information download mounting instruction.
Points de raccordement | |
screw M12 : |
Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence. | |
permitted power dissipation of the fuse-link: | 48 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Trouver votre contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com