L'Entreprise
Innovationen
Produits
The picture may show a similar product.
Référence 32459000
EQUES®60Classic
adaptateur de jeu de barres, 63 A
2 rails DIN réglables
81 x 200, avec câbles AWG 8 (10 mm²)
pour jeux de barres 12, 15, 20, 25, 30 x 5, 10 et barres profilées
Système
60Classic
Avantages produit
Conductor ends ultrasonically sealed.
Click mechanism when pushing onto the busbar.
Groupe de produits | 05 |
Sous-groupe | 24 |
Dimensions de l'emballage | 4 |
EAN | 4021267324599 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Normes
IEC 61439-1:2020
UL 508
Approbations
CSA , UL , DNV GL
for UL feeder circuits >250V
Type: EEC6063-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
Homologation CCC: no certification required
Details IEC | |
Normes | |
IEC 61439-1:2020 |
Electrical data IEC | |
Courant assigné (IEC): | 63 A |
Tension assignée (IEC) CA: | 690 V |
rated isolation voltage Ui AC: | 800 V |
Tension assignée de tenue aux chocs Uimp: | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 4,4 W.
(The power dissipation at full load would be 6,9 W.)
Details UL | |
Normes | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 65 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 7,5 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
SCCR: | 100 kA with JDDZ fuse Class CC, CF, J or T 60 A / 600 V AC |
Charactéristiques mécaniques | |
L x H x P: | 81 x 200 x 63 |
Poids: | 51,3 kg/100 |
Pôles: | 3 pôles |
pour jeux de barres: | 12, 15, 20, 25, 30 x 5, 10 et barres profilées |
There must be a clearance of at least 12 mm above the article to remove it from the busbar system. | |
Conseils |
For compact mounting of complete motor circuits with commercially available switchgear and safe mechanical and electrical connection to the busbar system. |
short-circuit withstandability: | the short-circuit capacity of the combination of adapter and motor starter depends on the motor starter |
for UL feeder circuits >250V |
Trouver votre contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com