Référence 32533000
EQUES®60Classic
adaptateur de jeu de barres 32 A
pour démarreur direct Allen-Bradley 140M-C, 140M-D
45 x 200, avec câbles AWG 10 (6 mm²)
pour jeux de barres 12, 15, 20, 25, 30 x 5, 10 et barres profilées
Système
60Classic
Avantages produit
Conductor ends ultrasonically sealed.
Click mechanism when pushing onto the busbar.
Groupe de produits | 05 |
Sous-groupe | 21 |
Dimensions de l'emballage | 4 |
EAN | 4021267325336 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Normes
IEC 61439-1:2020
UL 508
Approbations
CSA , UL , DNV GL
for UL feeder circuits >250V
Type: EEC6025-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
Homologation CCC: no certification required
Details IEC | |
Normes | |
IEC 61439-1:2020 |
Electrical data IEC | |
Courant assigné (IEC): | 32 A |
Tension assignée (IEC) CA: | 690 V |
rated isolation voltage Ui AC: | 800 V |
Tension assignée de tenue aux chocs Uimp: | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 1,6 W.
(The power dissipation at full load would be 2,5 W.)
Details UL | |
Normes | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 25 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 5 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 65 kA |
SCCR: |
30 kA with 140M-C, 140M-D 12,5 A / 600 V AC
65 kA with 140M-C, 140M-D 16 A / 480 V AC 65 kA with 140M-C, 140M-D 25 A / 480 V AC 50 kA with 140M-C, 140M-D 32 A / 480 V AC |
Charactéristiques mécaniques | |
L x H x P: | 45 x 200 x 63 |
Poids: | 32,5 kg/100 |
Pôles: | 3 pôles |
pour jeux de barres: | 12, 15, 20, 25, 30 x 5, 10 et barres profilées |
Points de raccordement | |
with leads | |
AWG10 (6 mm²) | |
wire stripping: | 9 mm |
There must be a clearance of at least 12 mm above the article to remove it from the busbar system. | |
short-circuit withstandability: | the short-circuit capacity of the combination of adapter and motor starter depends on the motor starter |