Description

Référence 01592000A

CRITO®CrossBoard

bornier de raccordement

avec bornes à ressort intégrées 1.5 - 16 mm², AWG 14 - 6

3 pôles

Système

CrossBoard® 125A / 250A

Groupe de produits 07
Sous-groupe 40
Dimensions de l'emballage 1
EAN 4021267015923
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Homologations

Normes

IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Approbations

IEC (CB) , UL

for UL feeder circuits >250V

Type: CR22-A

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

Homologation CCC: no certification required

Données techniques

Details IEC
Normes
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
Electrical data IEC
Courant assigné (IEC): 63 A
Tension assignée (IEC) CA: 690 V
rated isolation voltage Ui AC: 800 V
rated peak withstand current  Ipk max.: 10 kA

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 2,9 W.

(The power dissipation at full load would be 4,6 W.)

Supplementary data IEC

Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire.

Tension maximale IEC CA: 800 V
Tension maximale IEC CC: 800 V
current capacity (IEC) max.: 80 A
Details UL
Normes
UL 508
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
rated current (UL): 48 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR unprotected max.: 6 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 50 kA
with JDDZ fuse Class J 60 A / 600 V AC
Charactéristiques mécaniques
L x H x P: 22.5 x 160 x 115
Poids: 21,5 kg/100
Pôles: 3 pôles
front degree of protection: IP20
Points de raccordement
spring pulley connection
screw drive: 0,6x4
wire stripping: 18 mm
min. cross-section: 1,5 mm²
max. cross-section: 16 mm²
  
min. cross-section UL: AWG 14
max. cross-section UL: AWG 6
  

For leads per IEC :
1.5 - 16 mm² round stranded and finely stranded without wire-end ferrule
1.5 - 16 mm² finely stranded with wire-end ferrule*
1.5 - 10 mm² finely stranded with wire-end ferrule
1.5 - 10 mm² round solid

* Recommendation: 16 mm² crimped with Rittal crimping pliers for wire-end ferrules WM-Crimp, Weidmüller crimping tool PZ 16 or Phoenix Contact crimping pliers Crimpfox 25R

for leads per UL:
Cu AWG 14 - 6
Class B (UL486E)

Application notes

Les performances d'isolation de l'article dépendent des conditions d'installation.
for UL feeder circuits >250V

Links

Documentation

Trouver votre contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com