NH fuse switch-disconnector size 00, 160 A (33015)

The picture may show a similar product.

Description

Référence 33015000A

QUADRON®CrossBoard

NH fuse switch-disconnector size 00, 160 A

vis M8

raccordement par le haut ou par le bas

coming soon

Système

CrossBoard® 800 A

Avantages produit

Quick and safe conversion of the cable outlet side for top and bottom connection
Simple and safe snapping installation and contacting without tools
It is not necessary to remove the protection cover to connect the cables

Groupe de produits 09
Sous-groupe 70
Dimensions de l'emballage 1
EAN 4021267330156
ECLASS 6.1 27142108
ECLASS 7.1 27142108
ETIM 4.0 EC001040
ETIM 5.0 EC001040

Homologations

Normes

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

UL 4248-1

Approbations

UL , VDE

for UL feeder circuits >250V

UL file: E230163, UL category (for USA): IZLT2 https://www.ul.com

Données techniques

for fuse links size: NH 000, NH 00
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 12 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Details IEC
Normes
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
Courant assigné (IEC): 160 A
Tension assignée (IEC) CA: 800 V
Tension assignée (IEC) CC: 440 V
rated isolation voltage Ui AC: 1000 V
rated isolation voltage Ui DC: 500 V
Tension assignée de tenue aux chocs Uimp: 6 kV
Catégorie d'emploi CA: AC-23B (400V)
AC-23B (500V/125A)
AC-22B (690V)
AC-21B (690V)
AC-20B (1000V) at pollution degree 2

visible information required if used at more than 690V AC: do not switch under load
cond. short-circuit current with fuses (AC): 100 kA / 690 V
120 kA / 500 V (160 A)
approved wth fuse links of operation class: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 4,5 W.

(The power dissipation at full load would be 7,0 W.)

Supplementary data IEC

Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire.

Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence.
When several devices are used side-by-side in continuous operation, the rated load factor specified in IEC / EN 61439-1, Table 1, must be observed.
System component: degree of protection IP30 at front as per DIN EN 60529, degree of protection near terminal depends on installation
Details UL
Normes
UL 4248-1
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 160 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
Icc: 100 kA
Charactéristiques mécaniques
L x H x P: 106 x 200 x 110
Poids: 77,7 kg/100
Pôles: 3 pôles
front degree of protection: IP30

Busbar connector: externally tensioned contacting, convenient click mechanism

Points de raccordement
screw connection
M8
screw drive: SW13
min. cross-section: 1,5 mm²
max. cross-section: 95 mm²
re: 1.5 - 95 mm²
rm: 1.5 - 95 mm²
rm + AE: 1,5 - 70 mm²
f: 1.5 - 70 mm²
f + AE: 1.5 - 70 mm²
(f + AE may not fit with max. cross-section)
Md min.: 8,0 Nm
Md max.: 10,0 Nm
Not suitable for aluminium cables !
  

Accessories:
Clamp connection: Cu 1.5-70mm² s(r), f+AE; lam. Cu 12x1-10; 3Nm torque
single wedge clamp terminal: Cu, Al* 16-70mm² s(r), s(s), f+AE; 3Nm torque
tunnel terminal 3x Cu 1.5-16mm² s(r), f+AE; 3Nm torque

*Connections not maintenance-free if aluminium conductors are used.

Application notes

Not suitable for aluminium cables !
required spacing top: 50 mm
Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence.
permitted power dissipation of the fuse-link: 12 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.