busbar mounted fuse holder Class J (33421)

The picture may show a similar product.

Description

Part No.: 33421000

QUADRON®60Classic

busbar mounted fuse holder Class J

for fuse links Class J 1 - 30 A (21x57)

3P, with box terminal

connection top or bottom

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

System

60Classic

Advantages of the product

the product is based on the UL approval in category IZLT2 also listed in category NMTR (file E123577)

CrossLink® adapter technology
Fast and safe conversion of the connection for top or bottom; the parts under voltage remain shock protected
Simple and safe clicking into place and making contact
Safe connection through shock protection split into two
Busbar supports for flat busbars can be mounted above each other

Product group 16
Subgroup 21
pack size 1
EAN 4021267334215
ECLASS 6.1 27142190
ECLASS 7.1 27142190
ETIM 4.0 EC002705
ETIM 5.0 EC002705

Approvals

Standards

IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H

UL 4248-8

UL 4248-1

Approvals

UL

for UL feeder circuits >250V

type number: QCC-ClassJ30A

UL file: E230163, UL category (for USA): IZLT2 https://www.ul.com

UL file 2: E123577, UL category+ (for USA): NMTR https://www.ul.com

UL file: E230163, UL category (for Canada): IZLT8 https://www.ul.com

UL file 2: E123577, UL category+ (for Canada): NMTR7 https://www.ul.com

Technical data

for fuse links size: Class J 30 A
fuse links acc. to standard: UL 248-8
permitted power dissipation of the fuse-link: 5 W
Details IEC
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H

Electrical data

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 1.3 W.

(The power dissipation at full load would be 2.1 W.)

System component: degree of protection IP30 at front as per DIN EN 60529, degree of protection near terminal depends on installation
adapter module: front side degree of protection IP20 as per DIN EN 60529 (finger-safe)
Details UL
Standards
UL 4248-8
UL 4248-1
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
rated current (UL): 30 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
rated voltage (UL) DC: 600 V
for wires UL: Cu 75°C
SCCR: 200 kA
Mechanical data
W x H x D: 106 x 200 x 135
weight: 138.0 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars

Busbar connector: externally tensioned contacting, convenient click mechanism, simple conversion of the combination bases from 5 to 10mm-thick busbars

Terminal points
Not suitable for aluminium cables !
  
min. cross-section UL: AWG 14
max. cross-section UL: AWG 2/0
for wires UL: Cu 75°C
  

AWG 12 - AWG 2/0 stranded, equivalent 3,3 - 67,4 mm²
AWG 14 - AWG 10 solid, equivalent 215 - 5,3 mm²

Application notes

Not suitable for aluminium cables !
permitted power dissipation of the fuse-link: 5 W
for UL feeder circuits >250V

Links