Select product

for UL feeder circuits >250V

brace terminal (01760000)

The picture may show a similar product.

Description

Part No.: 01760 000

CRITO

brace terminal

Cu / Al 95 - 300 mm²

for busbars 20, 25, 30 x 5, 10 and section busbars

System

60Classic, centre feed unit, 100Energy

Advantages of the product

Klemme mit unverlierbaren Klemmschrauben, Übergreifen des Leiters möglich, Angabe von Nennquerschnitt und Anzugsdrehmoment auf der Klemme vermerkt, Kontaktierung der Leitung mit der Sammelschiene erfolgt über Kabelbett.

Product group 07
Subgroup 25
pack size 3
EAN 4021267017606
ECLASS 14.0 27250116
ETIM 5.0 EC000001
ETIM 8.0 EC000001
ETIM 10.0 EC000001

Approvals

Standards

IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Approvals

CSA , UL , DNV GL

type number: 529

EAC Type: TE-B

UL file: E123577, UL category (for USA): NMTR2 https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR8 https://www.ul.com

CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
Electrical data IEC
rated current (IEC): 500 A
rated voltage (IEC) AC: 690 V
rated peak withstand current  Ipk max.: 81.4 kA
rated short-time withstand current Icw (1.0 s) max.: 26.1 kA
Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) AC: 1000 V
max. permitted voltage (IEC) DC: 1500 V
current capacity (IEC) max. of the terminal: 600 A
min. permitted operation temperature -40°C
Details UL
Standards
UL 508
suitable for field-wiring
Electrical data UL
rated current (UL): 420 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
for wires UL: Cu 75°C
SCCR unprotected max.: 14 kA
1-pole, 3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 65 kA
SCCR: 3 terminals per pole at 1200A, 4 terminals per pole at 1600A
65 kA with any DIVQ/7 circuit breaker 1600 A / 480 V AC
65 kA with any DIVQ/7 circuit breaker 1200 A / 480 V AC
Mechanical data
W x H x D: 40 x 49 x 88
weight: 42,5 kg/100
for busbars: 20, 25, 30 x 5, 10 and section busbars
Terminal points
screw clamp connection
screw drive: S8
wire stripping: 38 mm
min. cross-section: 95 mm²
max. cross-section: 300 mm²
rm: 95 - 300 mm²
f: 95 - 300 mm²
ff: 240 - 300 mm²
sm: 95 - 300 mm²
Md min.: 24,0 Nm
Md max.: 36,0 Nm
Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
torque Alu: Alu: Md 30 - 36 Nm
  
min. cross-section UL: AWG 3/0
max. cross-section UL: MCM 600
torque (UL): 266 lb-in
for wires UL: Cu 75°C
Material properties
halogen-free: Yes

Application notes

Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
The insulation performance of the article depends on the installation conditions.

CSA certification available upon request


Annotation for UL feeder circuits > 250V:
only for 1 or 2 pole 120mm busbar systems