Company
Innovations
Products
for UL feeder circuits >250V
The picture may show a similar product.
Part No.: 01760 000
CRITO
brace terminal
Cu 95 - 300 mm², 250 - 600 MCM
for busbars 20, 25, 30 x 5, 10 and section busbars
System
60Classic, centre feed unit, 100Energy
Advantages of the product
Klemme mit unverlierbaren Klemmschrauben, Übergreifen des Leiters möglich, Angabe von Nennquerschnitt und Anzugsdrehmoment auf der Klemme vermerkt, Kontaktierung der Leitung mit der Sammelschiene erfolgt über Kabelbett.
| Product group | 07 |
| Subgroup | 25 |
| pack size | 3 |
| EAN | 4021267017606 |
| ECLASS 14.0 | 27250116 |
| ETIM 5.0 | EC000001 |
| ETIM 8.0 | EC000001 |
| ETIM 10.0 | EC000001 |
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Approvals
CSA , UL , DNV GL
type number: 529
EAC Type: TE-B
UL file: E123577, UL category (for USA): NMTR2 https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR8 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
CCC approval: no certification required
| Details IEC | |
| Standards | |
|
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
| Electrical data IEC | |
| rated current (IEC): | 500 A |
| rated voltage (IEC) AC: | 690 V |
| rated peak withstand current Ipk max.: | 81.4 kA |
| rated short-time withstand current Icw (1.0 s) max.: | 26.1 kA |
| Supplementary data IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
| max. permitted voltage (IEC) AC: | 1000 V |
| max. permitted voltage (IEC) DC: | 1500 V |
| current capacity (IEC) max. of the terminal: | 600 A |
| min. permitted operation temperature | -40°C |
| Details UL | |
| Standards | |
| UL 508 |
| suitable for field-wiring |
| Electrical data UL | |
| rated current (UL): | 420 A |
| rated voltage (UL) AC: | 600 V |
| rated frequency (UL): | 50 / 60 Hz |
| for wires UL: | Cu 75°C |
| SCCR unprotected max.: | 14 kA |
| 1-pole, 3 cycles (without OPD) @ 600 V AC | |
| SCCR protected max.: | 65 kA |
| SCCR: |
3 terminals per pole at 1200A, 4 terminals per pole at 1600A
65 kA with any DIVQ/7 circuit breaker 1600 A / 480 V AC 65 kA with any DIVQ/7 circuit breaker 1200 A / 480 V AC |
| Mechanical data | |
| W x H x D: | 40 x 49 x 88 |
| weight: | 42.5 kg/100 |
| for busbars: | 20, 25, 30 x 5, 10 and section busbars |
| Terminal points | |
| screw clamp connection | |
| screw drive: | S8 |
| wire stripping: | 38 mm |
| min. cross-section: | 95 mm² |
| max. cross-section: | 300 mm² |
| rm: | 95 - 300 mm² |
| f: | 95 - 300 mm² |
| ff: | 240 - 300 mm² |
| sm: | 95 - 300 mm² |
| Md min.: | 24.0 Nm |
| Md max.: | 36.0 Nm |
|
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
| torque Alu: | Alu: Md 30 - 36 Nm |
| min. cross-section UL: | AWG 3/0 |
| max. cross-section UL: | MCM 600 |
| torque (UL): | 266 lb-in |
| for wires UL: | Cu 75°C |
| Material properties | |
| halogen-free: | Yes |
| Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
| The insulation performance of the article depends on the installation conditions. | |
|
CSA certification available upon request |
|
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com