Company
Innovationen
Products
The picture may show a similar product.
Part No.: 36104000B
MOTUS®30Compact
hybrid motor starter, 3-pole
direct and reversing starter 0.18 - 2.4 A / switch for resistive loads 0.18 - 2.4 A
for busbars 12 x 5, 10
with CrossLink®Technology
System
30Compact 3P
Advantages of the product
4 functions integrated:
Right contactor
Left contactor
Motor protection relay
EMERGENCY STOP protection up to category 3
Installed width only 22.5mm
30 million electrical switching operations
Product group | 21 |
Subgroup | 06 |
pack size | 1 |
EAN | 4021267361044 |
ECLASS 6.1 | 27370804 |
ECLASS 7.1 | 27370804 |
ETIM 4.0 | EC001037 |
ETIM 5.0 | EC001037 |
Standards
EN 60947-1:2015
EN 60947-4-2:2012
EN 61439-1:2012
EN 50581:2012
EN ISO 13849-1:2015
UL 60947-1
Approvals
UL , CCC , Atex
for UL feeder circuits >250V
type number: 36110.1
UL file: E360470, UL category (for USA): NLDX https://www.ul.com
UL file: E360470, UL category (for Canada): NLDX7 https://www.ul.com
CCC certificate: 2019010304252617
Type-Examination Certificate: PTB13AT3001
Details IEC | |
Standards | |
EN 60947-1:2015 EN 60947-4-2:2012 EN 61439-1:2012 EN 50581:2012 EN ISO 13849-1:2015 |
Electrical data IEC | |
rated current (IEC): | 2.4 A |
rated voltage (IEC) AC: | 500 V |
min. operating voltage AC: | 42 V |
trigger characteristic: | Class 10A |
set nominal current: | Yes |
min. load current: | 0.18 A |
max. switching frequency: | 2 Hz |
switching cycles: | 30.000.000 |
safety level: | SIL3 |
reply contact: | 1 CO |
rated frequency (IEC): | 50 / 60 Hz |
rated isolation voltage Ui AC: | 500 V |
rated surge voltage Uimp : | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 3.5 W.
(The power dissipation at full load would be 5.5 W.)
Details UL | |
Standards | |
UL 60947-1 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 2 A |
rated voltage (UL) AC: | 500 V |
min. operating voltage AC: | 42 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 5 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
SCCR: | 100 kA with JDDZ fuse Class J 175 A / 600 V AC |
Mechanical data | |
W x H x D: | 22.5 x 160 x 156 |
weight: | 55.8 kg/100 |
poles: | 3-pole |
for busbars: | 12 x 5, 10 |
degree of protection: | IP20 |
vertical installation position: | Yes |
horizontal installation position: | No |
Terminal points | |
screw clamp connection | |
screw drive: | 0,8x4 |
wire stripping: | 8 mm |
min. cross-section: | 0.2 mm² |
max. cross-section: | 2.5 mm² |
Md min.: | 0.5 Nm |
Md max.: | 0.6 Nm |
min. cross-section UL: | AWG 24 |
max. cross-section UL: | AWG14 |
torque (UL): | 4,4 - 5,3 lb-in |
Screw terminals (solid round, flexible, flexible with wire-end ferrule) |
permitted degree of polution: | 2 |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com