Company
Innovationen
Products
The picture may show a similar product.
Part No.: 33162000
QUADRON®60Classic
NH fuse switch-disconnector size 3, 630 A
screw M12
with electromechanical fuse monitoring
connection top or bottom
for busbars 12, 20, 30 x 10 and section busbars
System
60Classic
Advantages of the product
Disconnectors are equipped with arc chambers.
The shock protection is split into 2 for safe connection of the conductors.
Product group | 09 |
Subgroup | 34 |
pack size | 1 |
EAN | 4021267331627 |
ECLASS 6.1 | 27142108 |
ECLASS 7.1 | 27142108 |
ETIM 4.0 | EC001040 |
ETIM 5.0 | EC001040 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
UL 4248-1
Approvals
IEC (CB) , UL , CCC , DNV GL
for UL feeder circuits >250V
type number: LTS-3
for fuse links size: | NH 3 |
fuse links acc. to standard: | IEC / HD 60269-2 |
live grip lugs required: | Yes |
permitted power dissipation of the fuse-link: | 48 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Details IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
rated current (IEC): | 630 A |
rated voltage (IEC) AC: | 690 V |
rated voltage (IEC) DC: | 250 V |
rated isolation voltage Ui AC: | 800 V |
rated isolation voltage Ui DC: | 250 V |
rated surge voltage Uimp : | 6 kV |
Utilisation category AC (IEC 60947-3) : | AC-23B (400V) AC-22B (690V) AC-21B (690V) |
Utilisation category DC (IEC 60947-3) : | DC specifications: 2 current paths (L1,L3) in series DC-22B (250V) |
cond. short-circuit current with fuses (AC): | 50 kA / 690 V |
approved wth fuse links of operation class: | gG |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 38.4 W.
(The power dissipation at full load would be 60.0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 725 V |
max. permitted voltage (IEC) DC: | 262 V |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
Entsprechend den angegeben AC- und DC- Schalteigenschaften und unter Berücksichtigung der Überlastbedingungen, sind gewisse Abstände zu geerdeten Metallteilen einzuhalten. Nähere Informationen auf Anfrage. Bei Verwendung als Trennschalter ist die Einhaltung der Abstände nicht erforderlich. |
|
Degree of protection IP30 at front, degree of protection near terminal depends on installation fuse monitoring: rated operating voltage AC 24-690V, DC 24-250V potential-free opener and closer: AC-15 24V/2A, (230V* 0.5A) DC-13 24V/1A, 60V 0.15A *pollution degree 2, surge category II auxiliary energy not required, for further information, see assembly manual |
Details UL | |
Standards | |
UL 4248-1 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 600 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR: | 100 kA |
Mechanical data | |
W x H x D: | 256 x 300 x 235 |
weight: | 824.0 kg/100 |
poles: | 3-pole |
for busbars: | 12, 20, 30 x 10 and section busbars |
front degree of protection: | IP30 |
Type of fastening: patented click mechanism
Terminal points | |
screw connection | |
M12 | |
screw drive: | SW18 |
Md min.: | 35.0 Nm |
Md max.: | 40.0 Nm |
Not suitable for aluminium cables ! | |
Accessories: |
Not suitable for aluminium cables ! | |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
live grip lugs required: | Yes |
permitted power dissipation of the fuse-link: | 48 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260