Company
Innovationen
Products
The picture may show a similar product.
Part No.: 33235000
in-line fuse switch-disconnector 160 A
screw M8 / clamp 70mm²
size 00
for busbars 30, 40, 50, 60 x 10
System
100Energy
Advantages of the product
Self-closing inspection holes are available in the cover.
Product group | 12 |
Subgroup | 51 |
pack size | 1 |
EAN | 4021267332358 |
ECLASS 6.1 | 27142108 |
ECLASS 7.1 | 27142108 |
ETIM 4.0 | EC001046 |
ETIM 5.0 | EC001046 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
IEC (CB) , CCC
type number: SLS-00
CCC certificate: 2004010302117261
for fuse links size: | NH 000, NH 00 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 12 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Details IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
rated current (IEC): | 160 A |
rated voltage (IEC) AC: | 800 V |
rated isolation voltage Ui AC: | 1000 V |
rated surge voltage Uimp : | 8 kV |
Utilisation category AC (IEC 60947-3) : | AC22 B (690 V) AC20 (800 V) Sichtbarer Hinweis notwendig: Nicht unter Last schalten in Fall von Betriebsspannung höher als 690 V
|
Utilisation category DC (IEC 60947-3) : | DC-20B max. voltage between the fuses: 1000V visible information required: Do not switch under load. |
cond. short-circuit current with fuses (AC): | 50 kA / 690 V |
approved wth fuse links of operation class: | gG |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 12.8 W.
(The power dissipation at full load would be 20.0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) DC: | 1000 V |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
Degree of protection IP30 at front, degree of protection near terminal depends on installation |
Mechanical data | |
W x H x D: | 50 x 455 x 120 |
weight: | 137.0 kg/100 |
for busbars: | 30, 40, 50, 60 x 10 |
Type of fastening: can be screwed onto drilled busbar,
M8, 12 - 14Nm torque,
or using terminal clamp,
adapter for 185-mm-System,
connection 70mm², screw M8, 12 - 14Nm torque,
connection clamp 1.5-70mm², 3Nm torque
wedge clamp terminal 16-70mm², 3Nm torque
Terminal points | |
screw M8 : |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
Reference |
with adapter (accessory) for the 185mm-System power |
permitted power dissipation of the fuse-link: | 12 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com