Company
Innovationen
Products
The picture may show a similar product.
Part No.: 32461000
EQUES®60Classic
busbar adapter 63 A
2 adjustable mounting rails
54 x 260, with leads AWG 8 (10 mm²)
for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars
System
60Classic
Advantages of the product
Conductor ends ultrasonically sealed.
Click mechanism when pushing onto the busbar.
Product group | 05 |
Subgroup | 24 |
pack size | 4 |
EAN | 4021267324612 |
ECLASS 6.1 | 27370304 |
ECLASS 7.1 | 27370304 |
ETIM 4.0 | EC001531 |
ETIM 5.0 | EC001531 |
Standards
IEC 61439-1:2020
UL 508
Approvals
CSA , UL , DNV GL
for UL feeder circuits >250V
type number: EEC6063-L
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
rated current (IEC): | 63 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 800 V |
rated surge voltage Uimp : | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 4.4 W.
(The power dissipation at full load would be 6.9 W.)
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 65 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
SCCR unprotected max.: | 7.5 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
SCCR: |
100 kA with MS45x 60 A / 480 V AC
100 kA with PKZ5 60 A / 480 V AC |
Mechanical data | |
W x H x D: | 54 x 260 x 63 |
weight: | 43.0 kg/100 |
poles: | 3-pole |
for busbars: | 12, 15, 20, 25, 30 x 5, 10 and section busbars |
There must be a clearance of at least 12 mm above the article to remove it from the busbar system. | |
Reference |
For compact mounting of complete motor circuits with commercially available switchgear and safe mechanical and electrical connection to the busbar system. |
short-circuit withstandability: | the short-circuit capacity of the combination of adapter and motor starter depends on the motor starter |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com