Company
Innovations
Products
The picture may show a similar product.
Part No.: 37717000A
QUADRON®185Power
in-line fuse switch-disconnector 400 A
size 2, 1-pole switchable
screw M12
prewired with 3x measuring transformers 400 A / 333 mV, accuracy class 1, with 6-pole plug connection
for busbars 30, 40, 60, 80, 100, 120 x 10
coming soon
System
185Power
Advantages of the product
Self-closing inspection holes are available in the cover.
Cover can be locked when closed.
Product group | 12 |
Subgroup | 64 |
pack size | 1 |
EAN | 4021267337179 |
ECLASS 6.1 | 27142108 |
ECLASS 7.1 | 27142108 |
ETIM 4.0 | EC001046 |
ETIM 5.0 | EC001046 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
type number: QU185-2 Pre-Assembled
for fuse links size: | NH 2 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 34 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Details IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
rated current (IEC): | 400 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 1000 V |
rated surge voltage Uimp : | 8 kV |
Utilisation category AC (IEC 60947-3) : | AC-23B 400A/400V |
Utilisation category DC (IEC 60947-3) : | DC-20B max. voltage between the fuses: 1000V visible information required: Do not switch under load. |
cond. short-circuit current with fuses (AC): | 100 kA / 690 V |
120 kA / 500 V | |
80 kA / 800 V (200A) | |
approved wth fuse links of operation class: | gG |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 38.4 W.
(The power dissipation at full load would be 60.0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
Degree of protection IP20 at front, degree of protection near terminal depends on installation |
Mechanical data | |
W x H x D: | 100 x 687 x 189 |
weight: | 543.0 kg/100 |
poles: | 3-pole |
for busbars: | 30, 40, 60, 80, 100, 120 x 10 |
CT can be integrated in the device: | ja |
CT can be integrated in the CT module: | nein |
front degree of protection: | IP20 |
degree of protection when open: | IP10 |
Type of fastening:
can be screwed onto drilled busbar, diameter 13mm, undrilled mounting with terminal clamp
connection:
screw connection M12
Terminal points | |
screw connection | |
screw M12 : |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
Reference |
The terminal compartment cover 33733 is always needed for the connection at top and when using cable lugs. |
permitted power dissipation of the fuse-link: | 34 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com