Company
Innovationen
Products
The picture may show a similar product.
Part No.: 01495000
universal busbar support
3-pole with internal screw holes
for busbars 12, 15, 20, 25, 30 x 5, 10
System
60Classic
Advantages of the product
With internal screw holes
can also be used as centre support
Product group | 06 |
Subgroup | 09 |
pack size | 10 |
EAN | 4021267014957 |
ECLASS 6.1 | 27400607 |
ECLASS 7.1 | 27400607 |
ETIM 4.0 | EC001166 |
ETIM 5.0 | EC001166 |
Standards
IEC 61439-1:2020
Approvals
DNV GL
type number: S610
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
rated voltage (IEC) AC: | 800 V |
rated frequency (IEC): | 50 / 60 Hz |
rated isolation voltage Ui AC: | 1000 V |
rated surge voltage Uimp : | 8 kV |
rated peak withstand current Ipk max.: | 73 kA |
rated short-time withstand current Icw (1.0 s) max.: | 34.2 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 0.0 W.
(The power dissipation at full load would be 0.0 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) DC: | 1500 V |
short-circuit capacity IEC / EN : Ipk max. = 73kA (busbar 30x10, 2 busbar supports in 250mm distance) go to calculation for 3-pole system (IEC) |
Mechanical data | |
W x H x D: | 20 x 191 x 50 |
weight: | 12.7 kg/100 |
poles: | 3-pole |
for busbars: | 12, 15, 20, 25, 30 x 5, 10 |
The insulation performance of the article depends on the installation conditions. | |
Reference |
Torque for the screws of the busbar support Md = 4Nm |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com