Company
Innovations
Products
The picture may show a similar product.
Part No.: 32429 000
EQUES®60Classic
busbar adapter 16 A
for direct starter Allen-Bradley 140M-RC2E, Eaton PKZM0, Siemens S00, Schneider Electric GV2 with spring terminals
45 x 200, with leads AWG 14 (2.5 mm²)
for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars
System
60Classic
Advantages of the product
Conductor ends ultrasonically sealed.
Click mechanism when pushing onto the busbar.
For switching devices with spring-loaded terminals
| Product group | 05 |
| Subgroup | 21 |
| pack size | 4 |
| EAN | 4021267324292 |
| ECLASS 6.1 | 27370304 |
| ECLASS 7.1 | 27370304 |
| ETIM 4.0 | EC001531 |
| ETIM 5.0 | EC001531 |
Standards
IEC 61439-1:2020
UL 508
Approvals
CSA , UL
type number: EEC6025
UL file: E123577, UL category (for USA): NMTR2 https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR8 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
CCC approval: no certification required
| Details IEC | |
| Standards | |
| IEC 61439-1:2020 |
| Electrical data IEC | |
| rated current (IEC): | 16 A |
| rated voltage (IEC) AC: | 690 V |
| rated isolation voltage Ui AC: | 800 V |
| rated surge voltage Uimp : | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 0.5 W.
(The power dissipation at full load would be 0.8 W.)
| Details UL | |
| Standards | |
| UL 508 |
| Electrical data UL | |
| rated current (UL): | 12 A |
| rated voltage (UL) AC: | 600 V |
| rated frequency (UL): | 50 / 60 Hz |
| Mechanical data | |
| W x H x D: | 45 x 200 x 63 |
| weight: | 31.0 kg/100 |
| poles: | 3-pole |
| for busbars: | 12, 15, 20, 25, 30 x 5, 10 and section busbars |
| Terminal points | |
| with leads | |
| AWG14 (2,5 mm²) | |
| wire stripping: | 9 mm |
| There must be a clearance of at least 12 mm above the article to remove it from the busbar system. | |
|
For compact mounting of complete motor circuits with commercially available switchgear and safe mechanical and electrical connection to the busbar system. |
|
|
the short-circuit capacity of the combination of adapter and motor starter depends on the motor starter |
|
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com