Company
Innovations
Products
for UL feeder circuits >250V
The picture may show a similar product.
Part No.: 36050 000A
CAPUS®CrossBoard
switch-disconnector-fuse, 3-pole
for fuses 10x38
16 A / 3P
double-breaking
operator independent switching (snap-action mechanism)
connection bottom
with CrossLink® interface
System
CrossBoard® 125A / 250A, CrossBoard® 800 A
Advantages of the product
3-pole switch-disconnector for safe galvanic isolation
Accommodates 10 x 38 fuse links in accordance with IEC 60269-2 from 0.5 A to 16 A
Lockable in the open or closed position using a locking device (accessory)
| Product group | 01 |
| Subgroup | 42 |
| pack size | 1 |
| EAN | 4021267360504 |
| ECLASS 6.1 | 27371401 |
| ECLASS 7.1 | 27371401 |
| ETIM 4.0 | EC001040 |
| ETIM 5.0 | EC001040 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
| for fuse links size: | 10x38 |
| fuse links acc. to standard: | IEC / HD 60269-2 |
| requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
| Details IEC | |
| Standards | |
|
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
| Electrical data IEC | |
| rated current (IEC): | 16 A |
| rated voltage (IEC) AC: | 400 V |
| rated frequency (IEC): | 50 / 60 Hz |
| rated surge voltage Uimp : | 4 kV |
| Utilisation category AC (IEC 60947-3) : | AC-22B (400V) |
| cond. short-circuit current with fuses (AC): | 50 kA |
| approved wth fuse links of operation class: | gG |
| Electrical data UL | |
| for wires UL: | Cu 60°C |
| Mechanical data | |
| W x H x D: | 22.5 x 180 x 88 |
| weight: | 17.5 kg/100 |
| poles: | 3-pole |
| degree of protection: | IP30 |
| Terminal points | |
| cage clamp connection | |
| screw drive: | 1x6,0 |
| wire stripping: | 10 mm |
| min. cross-section: | 1.5 mm² |
| max. cross-section: | 6 mm² |
| re: | 1 - 6 mm² |
| f: | 0.75 - 1.5 mm² |
| f + AE: | 0.75 - 1.5 mm² |
| (f + AE may not fit with max. cross-section) | |
| Md min.: | 1.2 Nm |
| Md max.: | 1.5 Nm |
| Not suitable for aluminium cables ! | |
| min. cross-section UL: | AWG 16 |
| max. cross-section UL: | AWG 10 |
| torque (UL): | 8,8 - 10,6 lb-in |
| for wires UL: | Cu 60°C |
| Not suitable for aluminium cables ! | |
|
4. Switch contact can be used as a signal switch: 24 V / 25 mA - 250 V / 16 A |
|
| requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
36919
000A
padlock for locking the switch
for: 36050
More
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com