Company
Innovations
Products
for UL feeder circuits >250V
The picture may show a similar product.
Part No.: 01068 000
CRITO®
universal conductor terminal
16 - 120 mm², AWG 6 - 250 MCM
for busbars flat busbars 5 mm
System
60Classic, 30Compact 3P
Advantages of the product
Terminal with integrated holding spring, captive clamping screw and opened terminal space.
Indication of nominal cross-section and tightening torque noted on the terminal.
| Product group | 07 |
| Subgroup | 18 |
| pack size | 25 |
| EAN | 4021267010683 |
| ECLASS 6.1 | 27141146 |
| ECLASS 7.1 | 27141146 |
| ETIM 4.0 | EC000001 |
| ETIM 5.0 | EC000001 |
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Approvals
CSA , UL
type number: 524
UL file: E123577, UL category (for USA): NMTR2 https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR8 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
CCC approval: no certification required
| Details IEC | |
| Standards | |
|
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
| Electrical data IEC | |
| rated current (IEC): | 250 A |
| rated voltage (IEC) AC: | 690 V |
| rated peak withstand current Ipk max.: | 27.7 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 0.0 W.
(The power dissipation at full load would be 0.0 W.)
| Supplementary data IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
| max. permitted voltage (IEC) AC: | 1000 V |
| max. permitted voltage (IEC) DC: | 1500 V |
| current capacity (IEC) max.: | 440 A |
| Details UL | |
| Standards | |
| UL 508 |
| suitable for field-installed conductors |
| Electrical data UL | |
| rated current (UL): | 255 A |
| rated voltage (UL) AC: | 600 V |
| rated frequency (UL): | 50 / 60 Hz |
| SCCR: | 18 kA |
| Mechanical data | |
| W x H x D: | 24 x 36 x 55 |
| weight: | 10.6 kg/100 |
| for busbars: | flat busbars 5 mm |
| Terminal points | |
| screw clamp connection | |
| screw drive: | SW17 |
| min. cross-section: | 16 mm² |
| max. cross-section: | 120 mm² |
| rm: | 16 - 120 mm² |
| f: | 16 - 120 mm² |
| f + AE: | 16 - 120 mm² |
| (f + AE may not fit with max. cross-section) | |
| Md min.: | 12.0 Nm |
| Md max.: | 18.0 Nm |
| Not suitable for aluminium cables ! | |
| Terminal space: | 17 x 15 |
| lam. Cu width: | 13 - 16 mm |
| lam. Cu thickness: | 3 - 10 mm |
| number of lam. Cu: | 1 |
| min. cross-section UL: | AWG 6 |
| max. cross-section UL: | MCM 250 |
| Not suitable for aluminium cables ! | |
| The insulation performance of the article depends on the installation conditions. | |
|
The suitability for feeder circuits (meeting the required feeder spacings) depends on the installation conditions. |
01413
000
cover cap, 3-pole
84 mm wide
84 x 200 x 55
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
More
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com