Company
Innovations
Products
The picture may show a similar product.
Part No.: 33206 000AC
NH fuse switch-disconnector size 00, 160 A
clamp 70 mm²
with electromechanical fuse monitoring
connection top or bottom
for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars
with CrossLink®Technology
Difference:production in China, no CrossLink
| Product group | 09 |
| Subgroup | 25 |
| pack size | 1 |
| EAN | 4021267332068 |
| ECLASS 6.1 | 27142108 |
| ECLASS 7.1 | 27142108 |
| ETIM 4.0 | EC001040 |
| ETIM 5.0 | EC001040 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
CCC
CCC certificate: 2010010302403934
| for fuse links size: | NH 000, NH 00 |
| fuse links acc. to standard: | IEC / HD 60269-2 |
| live grip lugs required: | Yes |
| permitted power dissipation of the fuse-link: | 12 W |
| requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
| Details IEC | |
| Standards | |
|
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
| Electrical data IEC | |
| rated current (IEC): | 160 A |
| rated voltage (IEC) AC: | 690 V |
| rated voltage (IEC) DC: | 250 V |
| rated isolation voltage Ui AC: | 800 V |
| rated isolation voltage Ui DC: | 250 V |
| rated surge voltage Uimp : | 2 kV |
| Utilisation category AC (IEC 60947-3) : | AC-22B 500V 160A AC-22B 690V 125A AC-23B 500V 125A AC-23B 400V 160A |
| cond. short-circuit current with fuses (AC): | 50 kA / 690 V |
| 80 kA / 500 V (160 A) | |
| approved wth fuse links of operation class: | gG |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 11.3 W.
(The power dissipation at full load would be 17.7 W.)
| Supplementary data IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
| max. permitted voltage (IEC) AC: | 725 V |
| max. permitted voltage (IEC) DC: | 262 V |
| further utilisation category DC (IEC 60947-3): | DC specifications: 2 current paths (L1,L3) in series DC-21B (220V) DC-22B (220V/63A) |
| A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
| for fuse links IEC 60269-2 / DIN VDE 0636-2 size 00 up to 12W power dissipation, with grip lugs under voltage | |
| Entsprechend den angegeben AC- und DC- Schalteigenschaften und unter Berücksichtigung der Überlastbedingungen, sind gewisse Abstände zu geerdeten Metallteilen einzuhalten. Nähere Informationen auf Anfrage. Bei Verwendung als Trennschalter ist die Einhaltung der Abstände nicht erforderlich. Bei Dauerbetrieb von mehreren Geräten nebeneinander ist der Bemessungsbelastungsfaktor nach VDE 0660 Teil 500 / EN60439-1, Tabelle 1 zu beachten. |
|
| System component: degree of protection IP30 at front as per DIN EN 60529, degree of protection near terminal depends on installation adapter module: degree of protection IP20 at front as per DIN EN 60529 (finger-safe) Fuse monitoring: rated operating voltage AC 24-690V, DC 24-250V potential-free opener and closer: AC-15 24V/2A, (230V* 0.5A) DC-13 24V/1A, 60V 0.15A *pollution degree 2, surge category II auxiliary energy not required, for further information, see assembly manual |
| Mechanical data | |
| W x H x D: | 106 x 200 x 172 |
| weight: | 180.0 kg/100 |
| poles: | 3-pole |
| for busbars: | 12, 15, 20, 25, 30 x 5, 10 and section busbars |
| front degree of protection: | IP30 |
Busbar connector: externally tensioned contacting, convenient click mechanism, simple conversion of the combination bases from 5 to 10mm-thick busbars
| Terminal points | |
| cage clamp connection | |
| screw drive: | S4 |
| wire stripping: | 20 mm |
| min. cross-section: | 1.5 mm² |
| max. cross-section: | 70 mm² |
| re: | 1.5 - 10 mm² |
| rm: | 16 - 70 mm² |
| f: | 1.5 - 70 mm² |
| f + AE: | 1.5 - 70 mm² |
| (f + AE may not fit with max. cross-section) | |
| Md min.: | 5.0 Nm |
| Md max.: | 6.0 Nm |
| Not suitable for aluminium cables ! | |
| Terminal space: | 12x9 |
|
2x 10 mm², 2x 16 mm² and 2x 25 mm² flexible with wire-end ferrules, identical cables placed side by side, crimping square |
|
| Not suitable for aluminium cables ! | |
| A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
| live grip lugs required: | Yes |
| permitted power dissipation of the fuse-link: | 12 W |
| requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
33915
000
connection for auxiliary line, for box terminal
flat connector EN 61210 6.3 x 0.8
for: QCB-NH00, QCS-NH00, QCS-160
More
79811
000
cover for cable lugs, top / bottom attachable
NH 00
for: 33200, 33208, 33329, 33394, 33398, 33420
More
33315
000
trim cover, 2 parts
for NH-LTS size 00
size 00
More
33317
000
trim strip, attachable at side
for NH-LTS size 00
size 00
More
78105
000
trim frame, double
232 x 210, not for 33221, 33222
size 00
More
78893
000
trim frame, single
130 x 210, not for 33221, 33222
size 00
More
33156
000
pilot switch
changeover 250 V AC / 5 A, 30 V DC / 4 A
More
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com