NH fuse switch-disconnector size 00, 160 A (33324)

The picture may show a similar product.

Description

Part No.: 33324000AC

NH fuse switch-disconnector size 00, 160 A

clamp 70 mm²

with electronic fuse monitoring

connection top or bottom

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

with CrossLink®Technology

Difference:production in China, no CrossLink

Product group 09
Subgroup 25
pack size 1
EAN 4021267333249
ECLASS 6.1 27142108
ECLASS 7.1 27142108
ETIM 4.0 EC001040
ETIM 5.0 EC001040

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

Technical data

for fuse links size: NH 000, NH 00
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 12 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
Rated current (IEC): 160 A
rated voltage (IEC) AC: 690 V
rated voltage (IEC) DC: 250 V
rated isolation voltage Ui AC: 800 V
rated isolation voltage Ui DC: 250 V
rated surge voltage Uimp : 6 kV
Utilisation category AC (IEC 60947-3) : AC-22B (500 V)
cond. short-circuit current with fuses (AC): 50 kA / 690 V
approved wth fuse links of operation class: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 11.3 W.

(The power dissipation at full load would be 17.7 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) AC: 725 V
max. permitted voltage (IEC) DC: 262 V
In accordance with the specified AC and DC switching properties and in consideration of the overload conditions, certain distances to earthed metal parts are to be adhered to. Please ask Wöhner for details.
When used as a disconnector, the spacings can be ignored.

When several devices are used side-by-side in continuous operation, the rated load factor specified in VDE 0660 Part 500 / EN 60 439-1, Table 1, must be observed.
System component: degree of protection IP30 at front as per DIN EN 60529, degree of protection near terminal depends on installation
adapter module: degree of protection IP20 at front as per DIN EN 60529 (finger-safe)

fuse monitoring:
without auxiliary energy
current may flow in and direction
one opener and one closer, potential-free
AC 5A/250V
DC 5A/30V
DC 0.2A/250V
red flashing indicator in case of defective fuse
automatic reset when replacing fuse
for further information, see assembly manual
Mechanical data
W x H x D: 106 x 200 x 137
weight: 117.0 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
front degree of protection: IP30

Busbar connector: externally tensioned contacting, convenient click mechanism, simple conversion of the combination bases from 5 to 10mm-thick busbars

Terminal points
Not suitable for aluminium cables !
  

Box terminal:
1.5 - 70 mm² flexible cables, directly or with wire-end ferrules*, depending on contour of the lead 95 mm² could be connectable
1.5 - 10 mm² solid round
16 - 70 mm² stranded round
2x 10 mm², 2x 16 mm² and 2x 25 mm² flexible with wire-end ferrules, identical cables placed side by side, crimping square
2x 10 - 35 mm² flexible identical cables placed side by side

lam. Cu. 9 - 13 mm wide
terminal space 13 mm x 13 mm

(*flexible cables of maximum cross-section may not fit when using wire-end ferrule)

Application notes

Not suitable for aluminium cables !
permitted power dissipation of the fuse-link: 12 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.

Links

Downloads

Accessories

03849000
lid interlock
for sealing wire
Size 00
More

33156000
pilot switch
changeover 250 V AC / 5 A, 30 V DC / 4 A
More

33315000
trim cover, 2 parts
for NH-LTS size 00
size 00
More

33317000
trim strip, attachable at side
for NH-LTS size 00
size 00
More

33915000
connection for auxiliary line, for box terminal
flat connector EN 61210  6.3 x 0.8
for: QCB-NH00, QCS-NH00, QCS-160
More

78105000
trim frame, double
232 x 210, not for 33221, 33222
size 00
More

78893000
trim frame, single
130 x 210, not for 33221, 33222
size 00
More

79811000
cover for cable lugs, top / bottom attachable
NH 00
for: 33200, 33208, 33329, 33394, 33398, 33420
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com