connection module (01592)

The picture may show a similar product.

Description

Part No.: 01592000A

CRITO®CrossBoard

connection module

with integrated spring terminals 1.5 - 16 mm², AWG 14 - 6

3-pole

System

CrossBoard® 125A / 250A, CrossBoard® 800 A

Product group 07
Subgroup 40
pack size 1
EAN 4021267015923
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Approvals

Standards

IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Approvals

IEC (CB) , UL

for UL feeder circuits >250V

type number: CR22-A

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
Electrical data IEC
rated current (IEC): 63 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated peak withstand current  Ipk max.: 10 kA

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 2.9 W.

(The power dissipation at full load would be 4.6 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) AC: 800 V
max. permitted voltage (IEC) DC: 800 V
current capacity (IEC) max.: 80 A
Details UL
Standards
UL 508
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
rated current (UL): 48 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR unprotected max.: 6 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 50 kA
with JDDZ fuse Class J 60 A / 600 V AC
Mechanical data
W x H x D: 22.5 x 160 x 115
weight: 21.5 kg/100
poles: 3-pole
front degree of protection: IP20
Terminal points
spring pulley connection
screw drive: 0,6x4
wire stripping: 18 mm
min. cross-section: 1.5 mm²
max. cross-section: 16 mm²
  
min. cross-section UL: AWG 14
max. cross-section UL: AWG 6
  

For leads per IEC :
1.5 - 16 mm² round stranded and finely stranded without wire-end ferrule
1.5 - 16 mm² finely stranded with wire-end ferrule*
1.5 - 10 mm² finely stranded with wire-end ferrule
1.5 - 10 mm² round solid

* Recommendation: 16 mm² crimped with Rittal crimping pliers for wire-end ferrules WM-Crimp, Weidmüller crimping tool PZ 16 or Phoenix Contact crimping pliers Crimpfox 25R

for leads per UL:
Cu AWG 14 - 6
Class B (UL486E)

Application notes

The insulation performance of the article depends on the installation conditions.
for UL feeder circuits >250V

Links

Downloads

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de