connection terminal plate, 3-pole (01570)

The picture may show a similar product.

Description

Part No.: 01570000A

CRITO®60Classic

connection terminal plate, 3-pole

10 - 120 mm², AWG 2 - 250 MCM, lam. Cu. 9 - 15,5 x 2,4 - 10

cover can be removed with tool only

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

System

60Classic

Advantages of the product

Terminals can be removed for connection of uncut conductors

Product group 07
Subgroup 45
pack size 1
EAN 4021267015701
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Approvals

Standards

IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Approvals

CSA , UL , DNV GL

for UL feeder circuits >250V

type number: 243-L

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
Electrical data IEC
rated current (IEC): 250 A
rated voltage (IEC) AC: 690 V
rated surge voltage Uimp : 6 kV
rated peak withstand current  Ipk max.: 56.3 kA
Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) AC: 1000 V
max. permitted voltage (IEC) DC: 1500 V
current capacity (IEC) max.: 440 A
Details UL
Standards
UL 508
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
rated current (UL): 255 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR unprotected max.: 10 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
SCCR: 100 kA with JDDZ fuse Class J 500 A / 600 V AC
100 kA with JDDZ fuse Class J 600 A / 480 V AC
35 kA with any DIVQ/7 circuit breaker 600 A / 600 V AC
50 kA with any DIVQ/7 circuit breaker 600 A / 480 V AC
65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC
Mechanical data
W x H x D: 81 x 200 x 84
weight: 53.5 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
Terminal points
cage clamp connection
wire stripping: 25 mm
min. cross-section: 10 mm²
max. cross-section: 150 mm²
re: 10 - 10 mm²
rm: 16 - 150 mm²
f: 16 - 120 mm²
f + AE: 10 - 120 mm²
(f + AE may not fit with max. cross-section)
Terminal space: 15 x 15
Md min.: 12.0 Nm
Md max.: 12.5 Nm
Not suitable for aluminium cables !

Application notes

Not suitable for aluminium cables !
The insulation performance of the article depends on the installation conditions.
for UL feeder circuits >250V

Links

Downloads

Accessories

01301000
single cover for terminals
for terminal plate 01243
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com