Inovações
Produtos
A imagem pode mostrar um produto similar.
Código da peça: 33515000
QUADRON®Panel Speed
chave seccionadora com fusíveis, 3 polos
parafuso M10, para acionamento rotativo externo
tamanho 1
double-breaking
operator independent switching (snap-action mechanism)
para montagem em placa
Sistema
Panel
Vantagens do produto
With spring-controlled switch mechanism for frequent switching as per utilisation category "A"
FLAG indicator shows the switch setting
Fuses can be changed safely and without tools thanks to double-breaking main contacts
Additional visible separating section by removing the cover incl. fuses
Can be used as mains disconnector as per IEC / EN 60204-1 (main switch)
Also as an Emergency Off switch in combination with the red-yellow door coupling twist handle
Switches can be installed 90° left/right horizontal, always with the same switch lug position
Grupo de produto | 15 |
Subgroup | 06 |
Unidade por pacote | 1 |
EAN | 4021267335151 |
ECLASS 6.1 | 27371401 |
ECLASS 7.1 | 27371401 |
ETIM 4.0 | EC001040 |
ETIM 5.0 | EC001040 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Approvals
IEC (CB) , VDE
Número de tipo: QCS-NH1
for fuse links size: | NH 1 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 23 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Dados IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Dados elétricos IEC | |
Corrente de medição (IEC): | 250 A |
Tensão de medição (IEC) AC: | 690 V |
Tensão nominal de isolamento: | 800 V |
Tensão suportável nominal de impulso Uimp: | 8 kV |
Utilisation category AC (IEC 60947-3) : | AC-23B (690V/200A) AC-23B (500V/250A) AC-22A (690V/250A) |
Utilisation category DC (IEC 60947-3) : | DC specifications: 2 current paths (L1,L3) in series DC-21B (100 V / 200 A) |
cond. short-circuit current with fuses (AC): | 50 kA / 690V |
approved wth fuse links of operation class: | gG |
Fuses gL/gG, size 1, 690V/250A for fuse links IEC 60269-2 / DIN VDE 0636-2 size 1 up to 23W power dissipation | |
Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals. | |
When several devices are used side-by-side in continuous operation, the rated load factor specified in VDE 0660 Part 500 / EN 60 439-1, Table 1, must be observed. | |
System component: degree of protection IP20 at front as per DIN EN 60529, dependent upon installation in the connection area; shock protection to DIN EN 50274 |
Dados mecânicos | |
L x A x P: | 184 x 314 x 191 |
Peso: | 528,0 kg/100 |
Polaridade: | 3 polos |
Montagem: | para montagem em placa |
pontos terminais | |
screw connection | |
M10 | |
screw drive: | SW16 |
Md min.: | 30,0 Nm |
Md max.: | 35,0 Nm |
permitted power dissipation of the fuse-link: | 23 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Encontre sua pessoa de contato
Para a página de contato
Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil
Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de
Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com