Référence 33198000
QUADRON®60Classic
sectionneur à fusible NH taille 00, 160 A, monté sur rail, raccordement par le haut / par le bas
borne à cage
raccordement par le haut ou par le bas
pour jeux de barres 12, 15, 20, 25, 30 x 5, 10 et barres profilées
avec CrossLink®Technology
Système
60Classic
Avantages produit
CrossLink® adapter technology
Fast and safe conversion of the connection for top or bottom; the parts under voltage remain shock protected
Simple and safe clicking into place and making contact
Safe connection through shock protection split into two
If flat busbars are used the device can be mounted covering the busbar support
Groupe de produits | 09 |
Sous-groupe | 24 |
Dimensions de l'emballage | 1 |
EAN | 4021267331986 |
ECLASS 6.1 | 27142108 |
ECLASS 7.1 | 27142108 |
ETIM 4.0 | EC001040 |
ETIM 5.0 | EC001040 |
Normes
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
UL 4248-1
Approbations
IEC (CB) , UL , VDE , CCC , DNV GL
for UL feeder circuits >250V
Type: QCB-NH00
for fuse links size: | NH 000, NH 00 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 12 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Details IEC | |
Normes | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
Courant assigné (IEC): | 160 A |
Tension assignée (IEC) CA: | 690 V |
Tension assignée (IEC) CC: | 440 V |
rated isolation voltage Ui AC: | 800 V |
rated isolation voltage Ui DC: | 500 V |
Tension assignée de tenue aux chocs Uimp: | 6 kV |
Catégorie d'emploi CA: | AC-21B (690 V) AC-22B (500 V) |
cond. short-circuit current with fuses (AC): | 50 kA / 690 V |
80 kA / 500 V (160 A) | |
approved wth fuse links of operation class: | gG |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 11,3 W.
(The power dissipation at full load would be 17,7 W.)
Supplementary data IEC | |
Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire. |
Tension maximale IEC CC: | 800 V |
further utilisation category AC (IEC 60947-3): | AC-20B (1000 V) at pollution degree 2 visible information required if used at more than 690V AC: do not switch under load |
further utilisation category DC (IEC 60947-3): | 2 contacts (L1,L3) in line
|
Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence. |
When several devices are used side-by-side in continuous operation, the rated load factor specified in IEC / EN 61439-1, Table 1, must be observed. | |
System component: degree of protection IP30 at front as per DIN EN 60529, degree of protection near terminal depends on installation adapter module: front side degree of protection IP20 as per DIN EN 60529 (finger-safe) |
Details UL | |
Normes | |
UL 4248-1 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 160 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
Icc: | 100 kA |
Charactéristiques mécaniques | |
L x H x P: | 106 x 200 x 97 |
Poids: | 100,0 kg/100 |
Pôles: | 3 pôles |
pour jeux de barres: | 12, 15, 20, 25, 30 x 5, 10 et barres profilées |
front degree of protection: | IP30 |
Busbar connector: externally tensioned contacting, convenient click mechanism, simple conversion of the combination bases from 5 to 10mm-thick busbars
Points de raccordement | |
cage clamp connection | |
screw drive: | S4 |
wire stripping: | 20 mm |
min. cross-section: | 1,5 mm² |
max. cross-section: | 70 mm² |
re: | 1.5 - 10 mm² |
rm: | 16 - 70 mm² |
f: | 1.5 - 70 mm² |
f + AE: | 1.5 - 70 mm² |
(f + AE may not fit with max. cross-section) | |
Alvéole de serrage: | 12x9 |
Md min.: | 5,0 Nm |
Md max.: | 6,0 Nm |
Not suitable for aluminium cables ! | |
min. cross-section UL: | AWG 12 |
max. cross-section UL: | AWG 2/0 |
torque (UL): | 44-53 lb-in |
2x 10 mm², 2x 16 mm² and 2x 25 mm² flexible with wire-end ferrules, identical cables placed side by side, crimping square |
Not suitable for aluminium cables ! | |
basé sur les capacités de commutation AC et DC et compte tenu des conditions de surcharge telle que données dans les normes mentionnées ci-dessus, les distances suivantes par rapport à des pièces métalliques mises à la terre doivent être respectés : |
|
required spacing top: | 100 mm |
required spacing at sides: | 50 mm |
Les unités de commutation à fusibles conformes à la norme IEC 60947-3 ne peuvent fonctionner au-delà de la tension de service nominale que si elles sont utilisées comme sectionneurs à fusible sans fonction de commutation de charge et cela jusqu'à la tension d'isolement assignée et sont marquées en conséquence. | |
permitted power dissipation of the fuse-link: | 12 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
for UL feeder circuits >250V |
Trouver votre contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com