Design verification according to IEC / EN 61439-1, -2

Wöhner stands for competence in the area of the busbar system technology. Good service for our customers is a matter for us. Therefore Wöhner also offers special support in the application of its systems. With this software, we support you in the preparation of design verification to IEC / EN 61439.

Design verification
Create a new project. The project data are provided in the download as *.xml, which can be read back later.

If you want to continue to work with the data of an existing project, upload therefore the file "bauartnachweis.xml".

Manufacturer of the assembly and issuer of the design verification

Company

User

Street, house number

Zip code

Place

Country

Information about the system

Client

Street, house number

Zip code

Place

Responsible person

Location

Usage

Issue this comment

Identifying characteristics of switchgear and controlgear assembly

Rated voltage Un [V] *1

Rated operating voltage Ue of the circuits [V]

Rated insulation voltage Ui PDF [V]

Rated impulse withstand voltage Uimp PDF [V]

Rated current InA [A]

Rated current of the circuits InC [A]

Setpoint rated peak withstand current Ipk PDF [kA]

Actual value of rated peak withstand current Ipk PDF [kA] *2

Setpoint rated short-time withstand current Icw [kA]

Actual value of rated short-time withstand current Icw [kA] *2

Setpoint rated conditional short-circuit current Icc [kA]

Actual value of rated conditional short-circuit current Icc [kA] *2

Rated load factor RDF PDF

Rated frequency fn [Hz]

Installation conditions

Access to switchgear and controlgear assembly

Issue this comment

Further characterizing features

The system was configured according to the user specified items (DIN EN 61439-1 Annex C)

With the assembly, the documentation was passed.

Issue this comment

Verification to 10.2.2 resistance to corrosion

Verification omitted since no risk of corrosion

Corrosion resistance of the cabinet see appendices

Corrosion resistance of the busbar components see appendices

Verification to 10.2.3.1 thermal stability of enclosures

Verification for the cabinet see appendices

Verification omitted since enclosures of metal

Verification for busbar components see appendices

Verification to 10.2.3.2 resistance to abnormal heat and fire due to internal electrical effects

Verification for the cabinet see appendices

Verification for busbar components see appendices

Verificationg to 10.2.4 resistance to ultra-violett (UV) radiation

Verification omitted since indoor installation

Verification for the cabinet see appendices

Verification to 10.2.7 marking

Product labeling suitable for site

Issue this comment

Verification to 10.4 clearances and creepage distances

The air and creepage distances are sufficiently large.

Critical clearance and creepage distances must also be checked during routine verification.

Issue this comment

Verification to 10.5 protection against electric shock and integrity of protective circuits

The protective conductor circuits and connections with the bodies of the switchgear assembly shall be sufficient. PDF

The internal resistance of the protective conductor connections is less than 0.1 [Ω].

Issue this comment

Verification to 10.6 incorporation of switching devices and components

Verification by assessment

Issue this comment

Verification to 10.7 internal electrical circuits and connections

The internal electrical connections were sufficiently dimensioned

Issue this comment

Verification to 10.8 terminals for external conductors

The terminals for external conductors are adequately sized

Issue this comment

Verification to 10.9 insulation properties

The power-frequency withstand voltage was detected

The impulse withstand voltage was detected

Issue this comment

Verification to 10.10 temperature rise

Verification by comparison with a similar existing system, in which the temperature-rise limits are respected (use of design rules) 10.10.3

Verification by calculation according to 10.10.4.2 (temperature equilibrium in the control cabinet, power dissipation of the device in continuous operation)

Verification by calculation according to 10.10.4.3 (IEC 60890) (temperature equilibrium in the control cabinet, power dissipation of the device in continuous operation)

Verification by using the calculation program of the cabinet manufacturer

Verification by using the calculation program of the manufacturer of air conditioning

Ensuring the cabinet temperature by cooling

Issue this comment

10.11 Short-circuit strength (determination of the setpoint)

Customer specification

Calculation based on the transformer table PDF

Calculated on the basis of the network and upstream short-circuit protection device e.g. NH-fuses PDF

Issue this comment

Verification of sufficient short-circuit strength

Verification omitted since set value smaller than 10 kA rms / 17 kA ipk (10.11.2)

Determination of the Ipk from the Wöhner website (detection by reference design; 10.11.3 (tabel 13) and 7) PDF

The calculated short-circuit strength of the system is higher or at least equal to the level of the target value

Issue this comment

10.12 Electromagnetic compatibility (EMC)

Only uses parts that comply with the conditions laid down in the product standard limits

Interference emission and immunity testing see Annex

Issue this comment

Verification to 10.13 mechanical function

The effectiveness of the mechanical actuators, locking devices and fasteners, including those in combination with removable parts that are not type-approved, was detected.

Issue this comment

For the project and the accuracy of details in design verification

First name

Last name

function

Piece of evidence for the proper execution of the investment in accordance with the project specifications

11.2 Degree of protection of enclosures

11.3 Air and creepage distances PDF

11.4 Protection against electric shock and integrity of protective circuits

11.5 Incorporation of built-in components

11.6 Internal electrical circuits and connections

11.7 Connections for external conductors PDF

11.8 Mechanical operation

11.9 dielectric properties demonstrated by insulation test [MΩ] *2

11.9 dielectric properties demonstrated by high-voltage test [kV] *2

11.10 Wiring, operational performance and function

For the proper execution implementation of the Routine verification

First name

Last name

Function

Handover of the system

Putting into service

Handed over documentation

Handed over maintenance instructions

*1Required field
*2Required field (at least one subject required)

Please note
These templates were developed by Wöhner with great care and are provided free of charge.

With the use of these templates you agree that the Wöhner GmbH & Co. KG assumes no liability for the accuracy, completeness, timeliness and usefulness of the individual data. Also for damage caused by downloading or upgrading the data in external systems, assumes all Wöhner GmbH & Co. KG accepts no liability. In particular, for damage to persons, property or pecuniary damage which may be as consequential damages directly or indirectly related to the use of data.

The Wöhner GmbH & Co. KG assumes the provision of the data no further obligations. We point out that the Software-/Hardwaredesignations and brand names of these companies enjoy trademark, patent or trademark protection in general.

I agree that the data which I give for the creation of the design verification acc. IEC / EN 61439-1, -2 is collected and saved electronically. I can cancel this agreement with message to Wöhner at any time. For further information please see the data privacy statement.

Trouver votre contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com