Company
Innovationen
Products
The picture may show a similar product.
Part No.: 31273000A
AMBUS®Panel
holder for cylindrical fuses
10 x 38 / 1P/N
32 A / 690 V, N integrated
N on left side
for mounting rail
System
Panel
Advantages of the product
large clamping range
holder for label
Product group | 17 |
Subgroup | 06 |
pack size | 12 |
EAN | 4021267312732 |
ECLASS 6.1 | 27142190 |
ECLASS 7.1 | 27142190 |
ETIM 4.0 | EC002705 |
ETIM 5.0 | EC002705 |
Standards
IEC 60269-1:2006
IEC 60269-3:2010
Approvals
CCC
type number: AES10x38I
CCC certificate: 21107317576
for fuse links size: | 10x38 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 3 W |
Details IEC | |
Standards | |
IEC 60269-1:2006 IEC 60269-3:2010 |
Electrical data IEC | |
rated current (IEC): | 32 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 690 V |
rated surge voltage Uimp : | 4 kV |
cond. short-circuit current with fuses (AC): | 100 kA / 400 V (32A) |
100 kA / 500 V (25A) | |
approved wth fuse links of operation class: | gG |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 0.6 W.
(The power dissipation at full load would be 0.9 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 725 V |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
for fuse links as per IEC / EN 60269-2 with permitted rated power dissipations up to max. 3W for gG/gL up to max. 1.2W for aM |
Mechanical data | |
W x H x D: | 18 x 81 x 58 |
weight: | 9.0 kg/100 |
poles: | 1-pole+N |
Mounting: | for mounting rail |
degree of protection: | IP20 |
front degree of protection: | IP20 |
Terminal points | |
cage clamp connection | |
min. cross-section: | 1.5 mm² |
max. cross-section: | 10 mm² |
Md min.: | 0.8 Nm |
Md max.: | 1.2 Nm |
Not suitable for aluminium cables ! |
Not suitable for aluminium cables ! | |
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
permitted power dissipation of the fuse-link: | 3 W |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com