Company
Innovationen
Products
The picture may show a similar product.
Part No.: 36202000A
BROOME10®60Classic
power supply 10 A
400 V AC / 24 V DC, with push-in terminals
for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars
System
60Classic
Advantages of the product
efficiency of 95% permits an intallation width of 45 mm
self-protected at short-circuit with intelligent re-start
no pre-fuse needed
overvoltage capacity up to 6 kV
Product group | 21 |
Subgroup | 42 |
pack size | 1 |
EAN | 4021267362027 |
ECLASS 6.1 | 27142325 |
ECLASS 7.1 | 27142325 |
ETIM 4.0 | EC002540 |
ETIM 5.0 | EC002540 |
Standards
IEC 61010-1:2010
IEC 61010-2-201:2013
UL 61010-1
UL 61010-2-201
Approvals
IEC (CB) , UL
for UL feeder circuits >250V
type number: BROOME10
UL file: E497002, UL category (for USA): NMTR. https://www.ul.com
UL file: E497002, UL category (for Canada): NMTR7. https://www.ul.com
Details IEC | |
Standards | |
IEC 61010-1:2010 IEC 61010-2-201:2013 |
Electrical data IEC | |
rated voltage (IEC) AC: | 480 V |
min. operating voltage AC: | 380 V |
output voltage DC: | 24 V |
output current: | 10 A |
voltage control: | No |
typical hold-up time (400 V): | 20 ms |
typical hold-up time (480 V): | 20 ms |
separation input / output: | SELV / PELV |
over-voltage protection: | 32 V |
parallel operation possible: | Yes |
serial operation possible: | Yes |
rated frequency (IEC): | 50 / 60 Hz |
rated isolation voltage Ui AC: | 800 V |
rated surge voltage Uimp : | 6 kV |
Further technical data: max. input inrush current: 1,5 A periodic and random deviation: 50 mVpp hold-up time (typical): 20 ms input / output separation: SELV / PELV output overvoltage protection: max. 32 V dc parallel installation to increase the power: up to 30 A without additional protection for more than 30 A each output has to be protected by a fuse 16 A serial installation to increase the voltage: up to 72 V dc (note: Ab at 60 V dc and more: no SELV) |
Details UL | |
Standards | |
UL 61010-1
UL 61010-2-201 |
for UL feeder circuits >250V |
Electrical data UL | |
rated voltage (UL) AC: | 480 V |
min. operating voltage AC: | 380 V |
rated frequency (UL): | 50 / 60 Hz |
Mechanical data | |
W x H x D: | 45 x 200 x 172 |
weight: | 71.8 kg/100 |
poles: | 3-pole |
for busbars: | 12, 15, 20, 25, 30 x 5, 10 and section busbars |
degree of protection: | IP30 |
vertical installation position: | Yes |
Terminal points | |
min. cross-section: | 0.2 mm² |
max. cross-section: | 2.5 mm² |
push-in terminal: |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com