Company
Innovations
Products
The picture may show a similar product.
Part No.: 03293 000
QUADRON Panel
NH fuse-base 600 A, panel mounting, for PV
incoming connection screw M10, outgoing connection to busbar 2x 40 x 10
size 2XL / 3L, 1P, with touch protection
for mounting plate
System
Panel
Advantages of the product
For one or two internal busbars 40x10mm.
Busbar fully shock protected by the contact cover.
The shock protection is split into 2.
| Product group | 10 |
| Subgroup | 13 |
| pack size | 3 |
| EAN | 4021267032937 |
| ECLASS 14.0 | 27142106 |
| ETIM 5.0 | EC000067 |
| ETIM 8.0 | EC000067 |
| ETIM 10.0 | EC000067 |
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016
type number: PVH-NH2XL/3L
| fuse links acc. to standard: | IEC / EN 60269-6 |
| permitted power dissipation of the fuse-link: | 100 W |
| Details IEC | |
| Standards | |
|
IEC 60269-1:2006 + A1:2009 + A2:2014 IEC 60269-2:2013 + A1:2016 |
| Electrical data IEC | |
| rated current (IEC): | 600 A |
| rated voltage (IEC) AC: | 1000 V |
| rated voltage (IEC) DC: | 1500 V |
| rated surge voltage Uimp : | 6 kV |
| short-circuit strength when protected by fuses: | 50 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 8.8 W.
(The power dissipation at full load would be 13.8 W.)
| Supplementary data IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
| max. permitted operation temperature | 55°C |
| Bei praxisgerechter Anordnung muss bezüglich Strombelastbarkeit, bezogen auf den Nennstrom der Sicherung, ein Reduktionsfaktor von 0,6 berücksichtigt werden. | |
| for fuse links IEC 60269-6 |
| Electrical data UL | |
| rated current (UL): | 600 A |
| rated voltage (UL) DC: | 1500 V |
| for wires UL: | Cu 90°C |
| Electrical data | |
| SCCR: | 15 kA |
| Mechanical data | |
| W x H x D: | 81 x 265 x 147 |
| weight: | 110.0 kg/100 |
| poles: | 1-pole |
| Mounting: | for mounting plate |
| Terminal points | |
| Not suitable for aluminium cables ! | |
| for wires UL: | Cu 90°C |
| Material properties | |
| halogen-free: | Yes |
| Not suitable for aluminium cables ! | |
| The insulation performance of the article depends on the installation conditions. | |
| permitted power dissipation of the fuse-link: | 100 W |
79449
000
grip lug cover
for NH fuse-base
NH 1 - 3
More
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com