busbar support

The picture may show a similar product.

Description

Part No.: 01231 000

busbar support

3-pole, with internal screw holes

for busbars double-T section

System

60Classic

Advantages of the product

Suitable as outer and centre supports
with internal screw holes.

Product group 06
Subgroup 09
pack size 3
EAN 4021267012311
ECLASS 14.0 27400607
ETIM 5.0 EC001166
ETIM 8.0 EC001166
ETIM 10.0 EC001166

Approvals

Standards

IEC 61439-1:2020

UL 508

Approvals

CSA , UL , DNV GL

for UL feeder circuits >250V

type number: S630-L

EAC Type: SB

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2020
Electrical data IEC
rated voltage (IEC) AC: 800 V
rated frequency (IEC): 50 / 60 Hz
rated isolation voltage Ui AC: 1000 V
rated surge voltage Uimp : 8 kV
rated peak withstand current  Ipk max.: 91 kA
rated short-time withstand current Icw (1.0 s) max.: 44 kA

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 0.0 W.

(The power dissipation at full load would be 0.0 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) DC: 1500 V
min. permitted operation temperature -40°C

short-circuit capacity IEC / EN :
Ipk max. = 91 kA (busbar TT 720mm², 2 busbar supports in 500 mm distance)
go to calculation for 3-pole system (IEC)

 

Details UL
Standards
UL 508
for UL feeder circuits >250V
Electrical data UL
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR unprotected max.: 30 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 200 kA
see downloads
Mechanical data
W x H x D: 26 x 200 x 123
weight: 59.1 kg/100
poles: 3-pole
for busbars: double-T section
Material properties
halogen-free: Yes

Application notes

The insulation performance of the article depends on the installation conditions.

Torque for the screws of the busbar support Md = 4Nm

for UL feeder circuits >250V

Links

Downloads

Accessories

covers

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com