Select product

for UL feeder circuits >250V

NH fuse switch-disconnector size 00, 160 A (33015)

The picture may show a similar product.

Description

Part No.: 33015000A

QUADRON®CrossBoard

NH fuse switch-disconnector size 00, 160 A

screw M8

connection top or bottom

coming soon

System

CrossBoard® 800 A

Advantages of the product

Quick and safe conversion of the cable outlet side for top and bottom connection
Simple and safe snapping installation and contacting without tools
It is not necessary to remove the protection cover to connect the cables

Product group 09
Subgroup 70
pack size 1
EAN 4021267330156
ECLASS 6.1 27142108
ECLASS 7.1 27142108
ETIM 4.0 EC001040
ETIM 5.0 EC001040

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

UL 4248-1

Approvals

UL , VDE

for UL feeder circuits >250V

UL file: E230163, UL category (for USA): IZLT2 https://www.ul.com

Technical data

for fuse links size: NH 000, NH 00
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 12 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
rated current (IEC): 160 A
rated voltage (IEC) AC: 800 V
rated voltage (IEC) DC: 440 V
rated isolation voltage Ui AC: 1000 V
rated isolation voltage Ui DC: 500 V
rated surge voltage Uimp : 6 kV
Utilisation category AC (IEC 60947-3) : AC-23B (400V)
AC-23B (500V/125A)
AC-22B (690V)
AC-21B (690V)
AC-20B (1000V) at pollution degree 2

visible information required if used at more than 690V AC: do not switch under load
cond. short-circuit current with fuses (AC): 100 kA / 690 V
120 kA / 500 V (160 A)
approved wth fuse links of operation class: gG

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 4.5 W.

(The power dissipation at full load would be 7.0 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
When several devices are used side-by-side in continuous operation, the rated load factor specified in IEC / EN 61439-1, Table 1, must be observed.
System component: degree of protection IP30 at front as per DIN EN 60529, degree of protection near terminal depends on installation
Details UL
Standards
UL 4248-1
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 160 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR: 100 kA
Mechanical data
W x H x D: 106 x 200 x 110
weight: 77.7 kg/100
poles: 3-pole
front degree of protection: IP30

Busbar connector: externally tensioned contacting, convenient click mechanism

Terminal points
screw connection
M8
screw drive: SW13
min. cross-section: 1.5 mm²
max. cross-section: 95 mm²
re: 1.5 - 95 mm²
rm: 1.5 - 95 mm²
rm + AE: 1,5 - 70 mm²
f: 1.5 - 70 mm²
f + AE: 1.5 - 70 mm²
(f + AE may not fit with max. cross-section)
Md min.: 8.0 Nm
Md max.: 10.0 Nm
Not suitable for aluminium cables !
  

Accessories:
Clamp connection: Cu 1.5-70mm² s(r), f+AE; lam. Cu 12x1-10; 3Nm torque
single wedge clamp terminal: Cu, Al* 16-70mm² s(r), s(s), f+AE; 3Nm torque
tunnel terminal 3x Cu 1.5-16mm² s(r), f+AE; 3Nm torque

*Connections not maintenance-free if aluminium conductors are used.

Application notes

Not suitable for aluminium cables !
required spacing top: 50 mm
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
permitted power dissipation of the fuse-link: 12 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
for UL feeder circuits >250V

Links

Downloads

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com