Select product

for UL feeder circuits >250V

hybrid motor starter, 3-pole (36109)

The picture may show a similar product.

Description

Part No.: 36109000A

MOTUS®CrossBoard

hybrid motor starter, 3-pole

electronic unit direct and reversing starter 0.075 - 0.6 A / switch for resistive loads 0.075 - 0.6 A

with CrossLink® interface

System

CrossBoard® 125A / 250A, CrossBoard® 800 A

Product group 21
Subgroup 01
pack size 1
EAN 4021267361099
ECLASS 6.1 27370804
ECLASS 7.1 27370804
ETIM 4.0 EC001037
ETIM 5.0 EC001037

Approvals

Standards

EN 60947-1:2015
EN 60947-4-2:2012
EN 61439-1:2012
EN 50581:2012
EN ISO 13849-1:2015

UL 60947-1

Approvals

UL , CCC , Atex

for UL feeder circuits >250V

type number: 36109.1

UL file: E360470, UL category (for USA): NLDX https://www.ul.com

UL file: E360470, UL category (for Canada): NLDX7 https://www.ul.com

CCC certificate: 2019010304252617

Type-Examination Certificate: PTB13AT3001

Technical data

Details IEC
Standards
EN 60947-1:2015
EN 60947-4-2:2012
EN 61439-1:2012
EN 50581:2012
EN ISO 13849-1:2015
Electrical data IEC
rated current (IEC): 0.6 A
rated voltage (IEC) AC: 500 V
min. operating voltage AC: 42 V
trigger characteristic: Class 10A
set nominal current: Yes
min. load current: 0.075 A
max. switching frequency: 2 Hz
switching cycles: 30.000.000
safety level: SIL3
reply contact: 1 CO
rated frequency (IEC): 50 / 60 Hz
rated isolation voltage Ui AC: 500 V
rated surge voltage Uimp : 6 kV

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 1.8 W.

(The power dissipation at full load would be 2.8 W.)

Details UL
Standards
UL 60947-1
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 0.6 A
rated voltage (UL) AC: 500 V
min. operating voltage AC: 42 V
rated frequency (UL): 50 / 60 Hz
SCCR unprotected max.: 5 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
SCCR: 100 kA with JDDZ fuse Class J 175 A / 600 V AC
Mechanical data
W x H x D: 22.5 x 160 x 120
weight: 50.9 kg/100
poles: 3-pole
degree of protection: IP20
vertical installation position: Yes
horizontal installation position: No
Terminal points
screw clamp connection
screw drive: 0,8x4
wire stripping: 8 mm
min. cross-section: 0.2 mm²
max. cross-section: 2.5 mm²
Md min.: 0.5 Nm
Md max.: 0.6 Nm
  
min. cross-section UL: AWG 24
max. cross-section UL: AWG14
torque (UL): 4,4 - 5,3 lb-in

Application notes

permitted degree of polution: 2
for UL feeder circuits >250V

Links

Downloads

Accessories

31567000
replacement fuse for MOTUS®
fuse 16 A for version 0.6 A and 2.4 A
10x38 gR
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com