Select product

for UL feeder circuits >250V

adapter 160 A (32690)

The picture may show a similar product.

Description

Part No.: 32690000A

EQUES®CrossBoard

adapter 160 A

90 x 160

for ABB Tmax XT1, Allen-Bradley 140G-G, Siemens 3VA10, 3VA11, 3VA51, Eaton PDG1

with CrossLink® interface

System

CrossBoard® 125A / 250A, CrossBoard® 800 A

Advantages of the product

Capable of feeding and bridging two CrossBoards simultaneously.

Product group 05
Subgroup 30
pack size 1
EAN 4021267326906
ECLASS 6.1 27370304
ECLASS 7.1 27370304
ETIM 4.0 EC001531
ETIM 5.0 EC001531

Approvals

Standards

IEC 61439-1:2020

UL 508

Approvals

UL

for UL feeder circuits >250V

type number: EQ90-AA

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2020
Electrical data IEC
rated current (IEC): 160 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 6 kV

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 6.3 W.

(The power dissipation at full load would be 9.8 W.)

Folgende notwendige Reduktionen wurden durch Prüfungen ermittelt:
Leistungsschalter Siemens:

  • Siemens 3VA11, Leitungsabgang unten: 144 A
  • Siemens 3VA11, Leitungsabgang oben: 136 A
  • Siemens 3VA51, Leitungsabgang unten: 125A
  • Siemens 3VA51, Leitungsabgang oben: 112 A
Details UL
Standards
UL 508
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 100 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR unprotected max.: 10 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
SCCR: 100 kA with any DIVQ/7 circuit breaker 125 A / 480 V AC
42 kA with any DIVQ/7 circuit breaker 125 A / 600 V AC
Mechanical data
W x H x D: 90 x 160 x 45
weight: 40.0 kg/100
poles: 3-pole

Application notes

short-circuit withstandability: the short-circuit capacity of the combination of adapter and MCCB depends on the MCCB
for UL feeder circuits >250V

Links

Downloads

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com