Company
Innovationen
Products
The picture may show a similar product.
Part No.: 33311000
QUADRON®60Classic
bus mounted fuse holder Class J
for fuse links Class J 225 - 400 A (54x181)
3P, with box terminal
connection top or bottom
for busbars 30 x 10 and section busbars
System
60Classic
Advantages of the product
the product is based on the UL approval in category IZLT2 also listed in category NMTR (file E123577)
Product group | 16 |
Subgroup | 33 |
pack size | 1 |
EAN | 4021267333119 |
ECLASS 6.1 | 27142190 |
ECLASS 7.1 | 27142190 |
ETIM 4.0 | EC002705 |
ETIM 5.0 | EC002705 |
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H
UL 4248-8
UL 4248-1
Approvals
CSA , UL
for UL feeder circuits >250V
type number: JC400B
UL file: E230163, UL category (for USA): IZLT2 https://www.ul.com
UL file 2: E123577, UL category+ (for USA): NMTR https://www.ul.com
UL file: E230163, UL category (for Canada): IZLT8 https://www.ul.com
UL file 2: E123577, UL category+ (for Canada): NMTR7 https://www.ul.com
CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org
for fuse links size: | Class J 400 A |
fuse links acc. to standard: | UL 248-8 |
permitted power dissipation of the fuse-link: | 38 W |
Details IEC | |
Standards | |
IEC 60269-1:2006 + A1:2009 + A2:2014 IEC 60269-2:2013 + A1:2016, Fuse system H |
Electrical data
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 30.0 W.
(The power dissipation at full load would be 46.8 W.)
Details UL | |
Standards | |
UL 4248-8
UL 4248-1 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Electrical data UL | |
rated current (UL): | 400 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
rated voltage (UL) DC: | 600 V |
for wires UL: | Cu 75°C |
SCCR: | 65 kA |
Mechanical data | |
W x H x D: | 256 x 285 x 122 |
weight: | 690.0 kg/100 |
poles: | 3-pole |
for busbars: | 30 x 10 and section busbars |
Terminal points | |
Not suitable for aluminium cables ! | |
min. cross-section UL: | AWG 4 |
max. cross-section UL: | MCM 600 |
for wires UL: | Cu 75°C |
tunnel terminal with hole of 23,0 mm diameter |
Not suitable for aluminium cables ! | |
Reference |
Shock protection through push-on covers. |
permitted power dissipation of the fuse-link: | 38 W |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com