Part No.: 01166 000
busbar connecting terminal 520 A
55 mm
for busbars 12, 15, 20 x 5, 10
System
60Classic, 30Compact 3P
| Product group | 07 |
| Subgroup | 33 |
| pack size | 12 |
| EAN | 4021267011666 |
| ECLASS 6.1 | 27400606 |
| ECLASS 7.1 | 27400606 |
| ETIM 4.0 | EC000713 |
| ETIM 5.0 | EC000713 |
Standards
IEC 61439-1:2020
CCC approval: no certification required
| Details IEC | |
| Standards | |
| IEC 61439-1:2020 |
| Electrical data IEC | |
| rated voltage (IEC) AC: | 690 V |
| rated peak withstand current Ipk max.: | 63.1 kA |
| rated short-time withstand current Icw (1.0 s) max.: | 21 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 2.5 W.
(The power dissipation at full load would be 3.9 W.)
| Supplementary data IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
| max. permitted voltage (IEC) AC: | 1000 V |
| max. permitted voltage (IEC) DC: | 1500 V |
| current capacity (IEC) max.: | 520 A |
| Mechanical data | |
| W x H x D: | 55 x 29 x 20 |
| weight: | 19.2 kg/100 |
| for busbars: | 12, 15, 20 x 5, 10 |
| permitted busbar displacement: | 1 |
| permitted spacing between systems: | 5 - 10 mm |
| Terminal points | |
| screw clamp connection | |
| M8 | |
| Md min.: | 9.6 Nm |
| Md max.: | 14.4 Nm |
| The insulation performance of the article depends on the installation conditions. | |
|
!!! Max. permitted busbar offset 1mm !!! 3 units are needed for a 3-pole connection. |
|