Company
Innovations
Products
The picture may show a similar product.
Part No.: 01166000
busbar connecting terminal 520 A
55 mm
for busbars 12, 15, 20 x 5, 10
System
60Classic, 30Compact 3P
Product group | 07 |
Subgroup | 33 |
pack size | 12 |
EAN | 4021267011666 |
ECLASS 6.1 | 27400606 |
ECLASS 7.1 | 27400606 |
ETIM 4.0 | EC000713 |
ETIM 5.0 | EC000713 |
Standards
IEC 61439-1:2020
Approvals
DNV GL
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
rated voltage (IEC) AC: | 690 V |
rated peak withstand current Ipk max.: | 63.1 kA |
rated short-time withstand current Icw (1.0 s) max.: | 21 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 2,5 W.
(The power dissipation at full load would be 3,9 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 1000 V |
max. permitted voltage (IEC) DC: | 1500 V |
current capacity (IEC) max.: | 520 A |
Mechanical data | |
W x H x D: | 55 x 29 x 20 |
weight: | 19,2 kg/100 |
for busbars: | 12, 15, 20 x 5, 10 |
permitted busbar displacement: | 1 |
permitted spacing between systems: | 5 - 10 mm |
Terminal points | |
screw clamp connection | |
M8 | |
Md min.: | 9,6 Nm |
Md max.: | 14,4 Nm |
The insulation performance of the article depends on the installation conditions. | |
Reference |
!!! Max. permitted busbar offset 1mm !!! 3 units are needed for a 3-pole connection. |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de