Inovações
Produtos
A imagem pode mostrar um produto similar.
Código da peça: 31273 000A
AMBUS®Panel
suporte para fusíveis cilíndricos
Size 10x38
10 x 38 / 1P/N
32 A / 690 V, N integrado
N do lado esquerdo
for mounting rail
Sistema
Panel
Vantagens do produto
large clamping range
holder for label
| Grupo de produto | 17 |
| Subgroup | 06 |
| Unidade por pacote | 12 |
| EAN | 4021267312732 |
| ECLASS 6.1 | 27142190 |
| ECLASS 7.1 | 27142190 |
| ETIM 4.0 | EC002705 |
| ETIM 5.0 | EC002705 |
Standards
IEC 60269-1:2006
IEC 60269-3:2010
Approvals
CCC
Número de tipo: AES10x38I
CCC certificate: 21107317576
| for fuse links size: | 10x38 |
| fuse links acc. to standard: | IEC / HD 60269-2 |
| permitted power dissipation of the fuse-link: | 3 W |
| Dados IEC | |
| Standards | |
|
IEC 60269-1:2006 IEC 60269-3:2010 |
| Dados elétricos IEC | |
| Corrente de medição (IEC): | 32 A |
| Tensão de medição (IEC) AC: | 690 V |
| Tensão nominal de isolamento: | 690 V |
| Tensão suportável nominal de impulso Uimp: | 4 kV |
| cond. short-circuit current with fuses (AC): | 100 kA / 400 V (32A) |
| 100 kA / 500 V (25A) | |
| approved wth fuse links of operation class: | gG |
Dissipação de energia do artigo:
A dissipação de energia em uma carga de 80% resulta em 0,6 W.
(A dissipação de energia em sua carga máxima seria 0,9 W.)
| Dados adicionais IEC | |
|
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
| tensão máxima IEC AC: | 725 V |
| A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. |
| for fuse links as per IEC / EN 60269-2 with permitted rated power dissipations up to max. 3W for gG/gL up to max. 1.2W for aM |
| Dados mecânicos | |
| L x A x P: | 18 x 81 x 58 |
| Peso: | 9,0 kg/100 |
| Polaridade: | 1 polo+N |
| Montagem: | for mounting rail |
| degree of protection: | IP20 |
| front degree of protection: | IP20 |
| pontos terminais | |
| cage clamp connection | |
| min. cross-section: | 1,5 mm² |
| max. cross-section: | 10 mm² |
| Md min.: | 0,8 Nm |
| Md max.: | 1,2 Nm |
| Not suitable for aluminium cables ! | |
| Not suitable for aluminium cables ! | |
| A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such. | |
| permitted power dissipation of the fuse-link: | 3 W |