chave seccion. de fusível NH, tam. 2, 400 A, p/ mont. em barramento, conexão sup / inf (33326)

A imagem pode mostrar um produto similar.

Descrição

Código da peça: 33326000

QUADRON®60Classic

chave seccion. de fusível NH, tam. 2, 400 A, p/ mont. em barramento, conexão sup / inf

parafuso M10

with electronic fuse monitoring

connection top or bottom

para barramentos 12, 20, 30 x 10 e barramentos de seção

Sistema

60Classic

Vantagens do produto

Disconnectors are equipped with arc chambers.
The shock protection is split into 2 for safe connection of the conductors.

Grupo de produto 09
Subgroup 31
Unidade por pacote 1
EAN 4021267333263
ECLASS 6.1 27142108
ECLASS 7.1 27142108
ETIM 4.0 EC001040
ETIM 5.0 EC001040

Aprovações

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

UL 4248-1

Approvals

IEC (CB) , UL , CCC , DNV GL

for UL feeder circuits >250V

Número de tipo: LTS-2

UL file: E230163, UL category (for USA): IZLT2 https://www.ul.com

CCC certificate: 2004010302117262

Dados técnicos

for fuse links size: NH 2
fuse links acc. to standard: IEC / HD 60269-2
live grip lugs required: Yes
permitted power dissipation of the fuse-link: 34 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Dados IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Dados elétricos IEC
Corrente de medição (IEC): 400 A
Tensão de medição (IEC) AC: 690 V
Tensão de medição (IEC) DC: 250 V
Tensão nominal de isolamento: 690 V
rated isolation voltage Ui DC: 250 V
Tensão suportável nominal de impulso Uimp: 6 kV
Utilisation category AC (IEC 60947-3) : AC-23B (400V)
AC-22B (500 V)
AC-21B (500 V)
cond. short-circuit current with fuses (AC): 50 kA / 690 V
approved wth fuse links of operation class: gG

Dissipação de energia do artigo:

A dissipação de energia em uma carga de 80% resulta em 28,8 W.

(A dissipação de energia em sua carga máxima seria 45,0 W.)

Dados adicionais IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

tensão máxima IEC AC: 725 V
tensão máxima IEC DC: 262 V
A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
for fuse links IEC 60269-2-1 (I) / DIN VDE 0636-201 size 2 up to 34W power dissipation, with grip lugs under voltage
Schutzart IP30 frontseitig, im Anschlussbereich vom Einbau abhängig

Elektronische Sicherungsüberwachung:
- Zur Erkennung von Sicherungsausfällen mit Bemessungsspannung AC 100V bis AC 690V
- Keine Hilfsenergie erforderlich; Versorgung über Netzspannung
- Hilfskontakte potentialfrei
- LED- Blinkmelder (rot/grün)
- Testtaster
- Weitere Informationen unter Downloads / Datenblatt

Dados UL
Standards
UL 4248-1
for UL feeder circuits >250V
Dados electricos UL
corrente nominal (UL): 400 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR: 100 kA
Dados mecânicos
L x A x P: 210 x 288 x 185
Peso: 572,0 kg/100
Polaridade: 3 polos
para barramentos: 12, 20, 30 x 10 e barramentos de seção
front degree of protection: IP30

Type of fastening: patented click mechanism

pontos terminais
screw connection
M10
screw drive: SW16
Md min.: 30,0 Nm
Md max.: 35,0 Nm
  

Accessories:
Clamp connection:  Cu 120-240mm² s(r), f+AE; lam. Cu 21x1-14; 6-8Nm torque
single wedge clamp terminal: Cu, Al* 120-240mm² s(r), s(s), f, f+AE; 6-8 Nm torque
double wedge clamp terminal: Cu  2x 70-120mm² s(r), s(s), f+AE;  6-8Nm torque

*Connections are not maintenance-free if aluminium conductors are used.

Instruções de Aplicação

A fuse-combination unit acc. to IEC 60947-3 can only be operated at a higher voltage than its rated voltage, if it is used as a fuse-disconnector without breaking capacity, up to its max. rated insulation voltage and labelled as such.
live grip lugs required: Yes
permitted power dissipation of the fuse-link: 34 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
for UL feeder circuits >250V

Links

Downloads

Acessórios

33143000
cobertura para conector de cabo, fixável na parte superior/inferior
para QCB-NH2
para: QCB-NH2
Mais

33146000
terminal prisma, duplo, para cabos de Cu
2x 70 - 120 mm²
tamanho 2
Mais

33148000
conjunto de conversão
para barramentos 5 mm
tamanho 2
Mais

33153000
moldura de  acabamento, única
248 x 330
tamanho 2
Mais

33155000
proteção para alça
para chave seccionadora de fusível NH tam. 1-3
para proteção da área traseira de manuseio
Mais

33156000
interruptor de sinalização
comutador 250 V AC / 5 A, 30 V DC / 4 A
Mais

33157000
bloqueio da tampa
para fio de selagem ou 3 cadeados de 4 - 7 mm
Tamanho 1 - 3
Mais

33164000
conexão tipo grampo para cabos de Cu
120 - 240 mm²
para: QCB-NH2, LTS-F 400, LTS 630
Mais

33167000
terminal prisma, único, para cabos em Cu e Al
50 - 240 mm²
Mais

33316000
cobertura para acabamento, 2 partes
para NH-LTS tamanho 2
tamanho 2
Mais

33418000
placa de conexão
para chave seccionadora de fusível NH tamanho 2
Mais

Similar products

33326000
QUADRON®60Classic
chave seccion. de fusível NH, tam. 2, 400 A, p/ mont. em barramento, conexão sup / inf
parafuso M10
with electronic fuse monitoring
connection top or bottom
para barramentos: 12, 20, 30 x 10 e barramentos de seção
Mais

33602000
QUADRON®60Classic
chave seccion. de fusível NH, tam. 2, 400 A, p/ mont. em barramento, conexão sup / inf
parafuso M10
connection top or bottom
para barramentos: 12, 20, 30 x 10 e barramentos de seção
Mais

Encontre sua pessoa de contato

Para a página de contato

Wöhner Sistemas
Eletrotécnicos Ltda.
Rua Antônio Galvão Pacheco, 185
18550-612, Boituva/SPl
Brasil

Linha direta de pedidos (Alemanha)
+49 9563 751 125
order@woehner.de

Linha direta de tecnologia (Alemanha)
+49 9563 751 508
support@woehner.com