Part No.: 01423 000A
CRITO®185Power
connection module with cover
for direct cable connection, box terminal, Cu 300 mm² / Al 240 mm²
angled
for Cu max. 300 mm² / Al max. 240 mm²
for busbars 30, 40, 60, 80, 100, 120 x 10
System
185Power
| Product group | 07 | 
| Subgroup | 54 | 
| pack size | 3 | 
| EAN | 4021267014230 | 
| ECLASS 6.1 | 27141146 | 
| ECLASS 7.1 | 27141146 | 
| ETIM 4.0 | EC000001 | 
| ETIM 5.0 | EC000001 | 
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
CCC approval: no certification required
| Details IEC | |
| Standards | |
| 
																		IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003  | 
																
| Electrical data IEC | |
| rated current (IEC): | 500 A | 
| rated voltage (IEC) AC: | 690 V | 
| rated peak withstand current Ipk max.: | 50 kA | 
| rated short-time withstand current Icw (0.5 s) max.: | 25 kA | 
| Supplementary data IEC | |
| 
																	 The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.  | 
															
| max. permitted voltage (IEC) AC: | 1000 V | 
| max. permitted voltage (IEC) DC: | 1500 V | 
| current capacity (IEC) max.: | 630 A | 
| Mechanical data | |
| W x H x D: | 42 x 118 x 110 | 
| weight: | 35.0 kg/100 | 
| poles: | 1-pole | 
| for busbars: | 30, 40, 60, 80, 100, 120 x 10 | 
| Terminal points | |
| cage clamp connection | |
| screw drive: | S6 | 
| wire stripping: | 55 mm | 
| min. cross-section: | 70 mm² | 
| max. cross-section: | 300 mm² | 
| Md min.: | 26.0 Nm | 
| Md max.: | 30.0 Nm | 
| 
																		Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions.  | 
															|
| 
																 Cu, Al: 70 - 240 mm² stranded round  | 
														|
| Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions.  | 
													|
| The insulation performance of the article depends on the installation conditions. | |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com