Company
Innovationen
Products
The picture may show a similar product.
Part No.: 01594000A
CRITO®CrossBoard
connection module
150 mm², for rear feeding of the CrossBoard
3-pole
connection top and bottom
for CrossBoard 250 A
NEW
System
CrossBoard® 125A / 250A
Product group | 07 |
Subgroup | 48 |
pack size | 1 |
EAN | 4021267015947 |
ECLASS 6.1 | 27141146 |
ECLASS 7.1 | 27141146 |
ETIM 4.0 | EC000001 |
ETIM 5.0 | EC000001 |
Standards
IEC 61439-1:2020
IEC 60999-1:1999
IEC 60999-2:2003
UL 508
Approvals
UL
for UL feeder circuits >250V
type number: CR-B-114-A2
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 IEC 60999-1:1999 IEC 60999-2:2003 |
Electrical data IEC | |
rated current (IEC): | 320 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 800 V |
rated surge voltage Uimp : | 6 kV |
rated peak withstand current Ipk max.: | 40 kA |
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 800 V |
max. permitted voltage (IEC) DC: | 800 V |
current capacity (IEC) max.: | 320 A |
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V | |
suitable for field-installed conductors |
Electrical data UL | |
rated current (UL): | 285 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
for wires UL: | Cu 75°C |
SCCR unprotected max.: | 10 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
SCCR: |
65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC
100 kA with JDDZ fuse Class J 400 A / 600 V AC |
Mechanical data | |
W x H x D: | 114 x 276 x 57 |
weight: | 94.8 kg/100 |
poles: | 3-pole |
front degree of protection: | IP20 |
Terminal points | |
screw clamp connection | |
screw drive: | S4 |
wire stripping: | 30 mm |
min. cross-section: | 35 mm² |
max. cross-section: | 150 mm² |
Md min.: | 4.0 Nm |
Md max.: | 6.0 Nm |
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
min. cross-section UL: | AWG 2 |
max. cross-section UL: | MCM 300 |
torque (UL): | 35 - 53 lb-in |
for wires UL: | Cu 75°C |
Connecting circular conductors: |
Suitable for aluminium cables. When using aluminium cables, observe the maintenance instructions. |
|
The insulation performance of the article depends on the installation conditions. | |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com